Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

York Single Package Air Conditioner ZXE12E2A3AA1A111A2
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Blower Rotation Check
Initial Setup
Ensure ZX units are properly phased at the factory
Is the blower rotating in the correct direction at start-up?
Electrical Connection Check
Is the electrical connection to the unit correctly phased?
Change the phasing of the Field Line Connection if misphased
High-leg Delta Power Supply Check
Measure voltage of A or L1 phase to ground
Measure voltage of B or L2 phase to ground
Gas Piping Cleaning
WARNING!
Pipe Preparation
Use a special pipe dope for assembling wrought iron or steel pipe.
Select the appropriate compound for pipe assembly
Cleaning Process
Clean all piping of dirt and scale by hammering on the outside of the pipe.
Blow out loose particles from the pipe.
Pre-Start-Up Check
Have all gas lines external to the unit been purged of air?
Burner Replacement
Preparation
Close main manual shut-off valve
Shut off all power to the unit
Disassembly
Open the union fitting upstream of the unit gas valve and downstream from the main manual shut-off valve
Remove screws holding each end of the manifold to the manifold supports
Disconnect wiring to the gas valve
Remove the manifold & gas valve assembly
Inspection and Replacement
Initial 10 Hours Belt Tension Check
Belt Drive Blower Adjustments
Adjust blower speed and belt tension
Verify proper sheave alignment
Tighten blower pulley set screws
Tighten motor sheave set screws
Post 10-12 Hours Run Time Checks
Re-check blower pulley set screws
Re-check motor sheave set screws
Re-check belt tension
Belt Tension Maintenance
Adjust Belt Tension
Loosen the three nuts (A and B on side and C on back) of motor mount slide plate.
Adjust tension by placing a flat head screwdriver into the belt tightening slots and applying pressure against the motor mounting plate.
Tighten the three loosened nuts (A, B and C).
Check Belt Deflection
Enter the deflection distance obtained (in mm).
Is the deflection distance 4mm (5/32")?
Re-tighten nuts (A, B and C) after adjustments are completed.
Access the parts list for your equipment in MaintainX.
Flue Extension Kit
1FE0416
Roof Curb
1RC0458
Roof Curb
1RC0456
Thru the Base Electrical and Thru the Curb Gas
1TB0401
Thru the Base Electrical and Thru the Curb Gas
1TB0402
Flue Extension Kit
1FE0416
Roof Curb
1RC0458
Roof Curb
1RC0456
Thru the Base Electrical and Thru the Curb Gas
1TB0401
Thru the Base Electrical and Thru the Curb Gas
1TB0402
Flue Extension Kit
1FE0416
Roof Curb
1RC0458
Roof Curb
1RC0456
Thru the Base Electrical and Thru the Curb Gas
1TB0401
Thru the Base Electrical and Thru the Curb Gas
1TB0402
MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX