Miura Steam Boiler LX-200
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Daily Chemical Feed Check
Warning: No work other than that clearly indicated below is to be carried out on the boiler. Failure to observe this precaution may result in injury.
Checking the Chemical Feeder
Confirm that the chemical feed is as required.
Confirm that sufficient liquid is present to properly dissolve chemicals.
Confirm that there is no air in the chemical feed pump or feed line.
Warning: Protective glasses and rubber gloves must be worn when adding chemical compounds. These compounds may cause sight loss, burns, and other injuries when they contact with skin or eyes.
If boiler chemical comes into direct contact with skin, immediately wash away using cold water.
If this chemical enters an eye, immediately wash away with cold water and seek medical attention.
Always follow the instructions of your water treatment personnel in terms of chemical dosage.
1 Daily Gas Pressure Check
Warning: No work other than that clearly indicated below is to be carried out on the boiler. Failure to observe this precaution may result in injury.
Open the main gas valve
Using the boiler’s gas pressure gauge, confirm whether the gas is pressurized to the required range (i.e., 3 to 5 PSI)
If the reading on the gas pressure gauge is not within the required range, immediately shutdown the boiler
If the reading on the gas pressure gauge is not within the required range, contact a MIURA sales office or your local dealer for further instruction.
Sign off on the daily gas pressure check
1 Daily Low Water Level Interlock Test
Warning: No work other than that clearly indicated below is to be carried out on the boiler. Failure to observe this precaution may result in injury.
Low Water Level Interlock Test
If the water volume, for any reason, falls below the pre-determined water volume, combustion will immediately be stopped and if it is not recovered after 15 sec after combustion shutoff, a warning alarm will be activated. The display will read, “WATER ALARM 1”.
Open the ball valve at the bottom of the LVC and allow time for the steam pressure to force the water out of the LVC.
When the low water cut-off probe loses contact with the water for more than 15 seconds, the boiler will shift to stand-by mode first and shut down 15 seconds, the alarm will sound and the BL11 Microcomputer will display “WATER ALARM 1”.
Sign off on the Low Water Level Interlock Test
1 Daily Steam Boiler Maintenance
Warning!
No work other than that clearly indicated below is to be carried out on the boiler. Failure to observe this precaution may result in injury.
To keep your MIURA boilers running in optimum condition, be sure to check the following daily:
a) CHEMICAL FEED PUMP
i. Proper chemical feed.
ii. No air in the chemical feed pump or lines.
b) WATER SOFTENER
i. Boiler Make-up water is completely soft (use a test kit sensitive to less than 1.0 PPM).
ii. Make sure the water softener timer or softener flow meter is working every day.
1 Daily Steam Pressure Check
Warning: No work other than that clearly indicated below is to be carried out on the boiler. Failure to observe this precaution may result in injury.
Startup the boiler as described in Section 8.1: Boiler Startup.
Confirm that the reading on the steam pressure gauge is in the normal range, and that the gauge pointer is not swinging wildly.
Warning: If the steam pressure is not within the normal range, immediately shutdown the boiler and contact a MIURA sales office or your local dealer for further instruction. Continued use of the boiler with abnormal steam pressure levels may result in boiler damage, which in turn could lead to injury.
Sign off on the daily steam pressure check
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX