Daikin Air Conditioner Outdoor Unit RKC25PVMM
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Outer Panels Maintenace
Safety Precautions
Waited for 10 minutes after turning off all power supplies?
Removal Procedure
Remove the screw of the stop valve cover
Pull down and remove the stop valve cover
Ensure the 3 hooks are fitted when reassembling
Remove the 3 screws, and then the top panel
Remove the 6 screws of the front panel
Lift up the right side of the front panel and unfasten the 2 hooks
Thermistor Maintenance
Warning: Wait for 10 minutes after turning off all power supplies before disassembling
Removal Procedure
Pull out the discharge pipe temperature thermistor
Ensure the fixture for the thermistor is not lost
Cut the clamp
Check for sound blanket (back) and remove if present
Pull out the outdoor heat exchanger thermistor and remove the thermistor ASSY
Ensure the clip for the thermistor is not lost
Outdoor Fan, Fan Motor Maintenance
Removal Procedure
Wait for 10 minutes after turning off all power supplies before starting disassembly
Outdoor Fan Removal
Remove the nut (M6 size) and then the outdoor fan
Align the mark of the outdoor fan with the D-cut section of the motor shaft when reassembling
Fan Motor Disconnection
Disconnect the connector depending on the model
Note the location of connectors [S70] and [S71] as they differ
Fan Motor Lead Wire Release
Reactor, Partition Plate Maintenance
Warning: Wait for 10 minutes or more after turning off all power supplies before disassembling work
Remove the 2 screws of the reactor
Slide the reactor upward to unfasten the 2 hooks
Remove the reactor
Remove the 2 screws, and then the partition plate
Reassembly Instructions
Fit the hole on the partition plate to the hook on the bottom frame
Compressor Maintenance
Safety Precautions
Wait for 10 minutes after turning off all power supplies before disassembling work
Ensure pipes and parts heated by the gas brazing machine are cool to avoid burns
Ventilate the room if refrigerant gas leaks during work
Prepare wet cloth to extinguish fire immediately in case refrigerant oil catches fire
Environmental Cautions
Do not discharge refrigerant gas into the atmosphere
Collect all refrigerant gas
Restore piping by non-oxidation brazing
MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX