Bradford White Water Heater EF100T199E3NA2
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Flue Baffle Inspection
Service Procedure XIV — Flue Baffle Inspection and Replacement
Warning: Heater components can be hot during this procedure; take precautions to avoid injury.
Disassemble the heater per the Disassembly Procedure for Access to Anodes & Flue Baffles.
Remove the flue baffles with pliers
Remove 8 two-inch baffles
Remove 2 four-inch baffles
Visually inspect the baffles
Check for normal oxidation
Replace baffle if deteriorated oxidation or missing restrictors are found
Burner Tube Inspection
Service Procedure III — Burner Tube Inspection & Replacement
WARNING — Heater components can be hot during this procedure; take precautions to avoid injury.
Burner Tube Removal
Turn the main power switch off and unplug the water heater, then turn off the gas supply.
Remove the surround cover, then disconnect the gas connection, PVC venting, wire harness, and silicone tubing from the gas valve.
Disconnect the wire harness from the blower assembly.
Remove the two screws holding the hot surface igniter and flame sensor and carefully remove them (for Direct Spark Ignition models, remove the spark rod bracket screws and spark rod instead).
Remove the four nuts holding the burner transition, lift the blower/gas valve/transition assembly off, and set the gasket aside.
Remove the burner tube from the burner mounting insert.
Anode Rod Inspection
Service Procedure XIV — Anode Inspection and Replacement
Turn off the water supply and drain the water heater
Disassemble the heater for access to anodes and flue baffles
Locate and remove the anode rods using a 1-1/16 in. hex socket
Visually inspect each anode rod for depletion
Apply thread sealing tape or compound and reinstall the anode rods
Restore the water supply and check for leaks
Reinstall the collector cover
Reinstall the collector insulation and control panel
Spark Rod Gap Inspection
Service Procedure IX — Spark Rod Gap Inspection and Adjustment (Direct Spark Ignition models)
Remove the combustion system per the Combustion System Removal procedure
Measure the spark gap between the spark rod and burner tube
Is the spark gap within the acceptable range of 3/16 in. to 1/4 in.?
If out of range, carefully bend the spark rod
Re-measure to confirm the gap is within 3/16 in. to 1/4 in. after bending
Reinstall the combustion system
Check several ignitions to confirm the burner lights smoothly
Intake Pressure Switch Testing
Service Procedure XII — Intake Pressure Testing (models prior to serial "CF" only)
Check continuity through the normally closed intake pressure switch if the blower does not energize
Refer to the vent safety switch, exhaust pressure switch, or blower testing procedures if the intake pressure switch is not faulty
Check continuity through the switch if the purge LED does not illuminate within the expected time
Confirm the inlet tube pressure tap reads at least -1.2 in. W.C. using a manometer
Remove the hose from the intake pressure switch and restart the heater to see if the purge LED illuminates
Isolate the heater from the intake vent system and restart again to isolate a switch versus vent-system fault if the purge LED illuminates
Check whether the intake vent system is obstructed and clear any obstruction found
Call technical support if no cause is found
MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX