MaintainX, an Autodesk company
EnterprisePricing
Bradford White

Bradford White Water Heater EF100T1503XA2

Need answers fast?
Explore the manual using AI.

Bradford White Water Heater EF100T1503XA2
Bradford White Water Heater EF100T1503XA2

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Bradford White Water Heater EF100T1503XA2

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Bradford White Water Heater EF100T1503XA2

Bradford White Water Heater EF100T1503XA2

Create an account to install this asset package.

Maintenance Plans for Bradford White Water Heater Model EF100T1503XA2

Integrate maintenance plans directly into your work orders in MaintainX.

Thermostat Circuit Testing

Check mark

Service Procedure I — Thermostat Circuit Testing

Check mark

Error code 32

Check mark

Unplug electrical power to the water heater

Check mark

Check continuity of the wire harness to the sensor

Check mark

Check sensor resistance against the temperature/resistance table

Check mark

Restore power and run the heater through a heating cycle

Check mark

Error code 65 (high water temperature)

Check mark

Turn power off and draw water to cool the tank below 120°F

Check mark

Check that the sensor is fully inserted into the well and its clip is undamaged

Run this procedureArrow right

Burner Tube Inspection

Check mark

Service Procedure III — Burner Tube Inspection & Replacement

Check mark

WARNING — Heater components can be hot during this procedure; take precautions to avoid injury.

Check mark

Burner Tube Removal

Check mark

Turn the main power switch off and unplug the water heater, then turn off the gas supply.

Check mark

Remove the surround cover, then disconnect the gas connection, PVC venting, wire harness, and silicone tubing from the gas valve.

Check mark

Disconnect the wire harness from the blower assembly.

Check mark

Remove the two screws holding the hot surface igniter and flame sensor and carefully remove them (for Direct Spark Ignition models, remove the spark rod bracket screws and spark rod instead).

Check mark

Remove the four nuts holding the burner transition, lift the blower/gas valve/transition assembly off, and set the gasket aside.

Check mark

Remove the burner tube from the burner mounting insert.

Run this procedureArrow right

Intake Pressure Switch Testing

Check mark

Service Procedure XII — Intake Pressure Testing (models prior to serial "CF" only)

Check mark

Check continuity through the normally closed intake pressure switch if the blower does not energize

Check mark

Refer to the vent safety switch, exhaust pressure switch, or blower testing procedures if the intake pressure switch is not faulty

Check mark

Check continuity through the switch if the purge LED does not illuminate within the expected time

Check mark

Confirm the inlet tube pressure tap reads at least -1.2 in. W.C. using a manometer

Check mark

Remove the hose from the intake pressure switch and restart the heater to see if the purge LED illuminates

Check mark

Isolate the heater from the intake vent system and restart again to isolate a switch versus vent-system fault

Check mark

Check whether the intake vent system is obstructed and clear any obstruction found

Check mark

Call technical support if no cause is found

Run this procedureArrow right

Blower Testing

Check mark

Service Procedure V — Blower Testing & Replacement

Check mark

WARNING — 120-volt potential exposure; use caution making voltage checks.

Check mark

Confirm the blower energizes when the thermostat calls for heat

Check mark

Check for 120VAC across the terminal-block black and white wires

Check mark

Check for 120VAC at the ignition module/control board and blower wiring

Check mark

Repair or replace the harness or blower as indicated

Check mark

Check if the blower energizes but seems weak

Check mark

Check amp draw on the black blower-motor lead (should read 0.6–3.0 amps)

Check mark

Confirm the blower wheel is secure on the motor shaft

Run this procedureArrow right

Spark Rod Gap Inspection

Check mark

Service Procedure IX — Spark Rod Gap Inspection and Adjustment (Direct Spark Ignition models)

Check mark

Remove the combustion system per the Combustion System Removal procedure

Check mark

Measure the spark gap between the spark rod and burner tube

Check mark

Is the spark gap within the acceptable range of 3/16 in. to 1/4 in.?

Check mark

Adjust the spark rod if the gap is out of range

Check mark

Support the spark rod near the ceramic insulator with pliers

Check mark

Bend the end near the burner tube with needle-nose pliers

Check mark

Re-measure to confirm the gap is within 3/16 in. to 1/4 in. after bending

Check mark

Reinstall the combustion system

Run this procedureArrow right

Unlock
efficiency with MaintainX Assist

MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Bradford White

Explore Other Assets