MaintainX, an Autodesk company
EnterprisePricing
Bradford White

Bradford White Water Heater EF60T1503XA2

Need answers fast?
Explore the manual using AI.

Bradford White Water Heater EF60T1503XA2
Bradford White Water Heater EF60T1503XA2

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Bradford White Water Heater EF60T1503XA2

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Bradford White Water Heater EF60T1503XA2

Bradford White Water Heater EF60T1503XA2

Create an account to install this asset package.

Maintenance Plans for Bradford White Water Heater Model EF60T1503XA2

Integrate maintenance plans directly into your work orders in MaintainX.

Intake Pressure Switch Testing

Check mark

Service Procedure XII — Intake Pressure Testing (models prior to serial "CF" only)

Check mark

Check continuity through the normally closed intake pressure switch if the blower does not energize

Check mark

Refer to the vent safety switch, exhaust pressure switch, or blower testing procedures if the intake pressure switch is not faulty

Check mark

Check continuity through the switch if the purge LED does not illuminate within the expected time

Check mark

Confirm the inlet tube pressure tap reads at least -1.2 in. W.C. using a manometer

Check mark

Remove the hose from the intake pressure switch and restart the heater to see if the purge LED illuminates

Check mark

Isolate the heater from the intake vent system and restart again to isolate a switch versus vent-system fault

Check mark

Check whether the intake vent system is obstructed and clear any obstruction found

Check mark

Call technical support if no cause is found

Run this procedureArrow right

Exhaust and Blocked Vent Pressure Switch Testing

Check mark

Service Procedures VI — Exhaust Pressure Switch / Blocked Vent Pressure Switch Testing

Check mark

Confirm the blower energizes

Check mark

Does the purge LED or error code clear within 5 minutes?

Check mark

Check exhaust collector pressure at the pressure tap with a manometer

Check mark

Inspect the combustion system area and control panel

Check mark

Exhaust/Blocked Vent Pressure Switch Replacement

Check mark

Turn the main power switch off

Check mark

Slide back the rubber escutcheon and remove the service panel access cover

Check mark

Disconnect the silicone tubing and wire leads from the pressure switch

Run this procedureArrow right

Spark Rod Gap Inspection

Check mark

Service Procedure IX — Spark Rod Gap Inspection and Adjustment (Direct Spark Ignition models)

Check mark

Remove the combustion system per the Combustion System Removal procedure

Check mark

Measure the spark gap between the spark rod and burner tube

Check mark

Is the spark gap within the acceptable range of 3/16 in. to 1/4 in.?

Check mark

Adjust the spark rod if the gap is out of range

Check mark

Support the spark rod near the ceramic insulator with pliers

Check mark

Bend the end near the burner tube with needle-nose pliers

Check mark

Re-measure the spark gap to confirm it is within 3/16 in. to 1/4 in.

Check mark

Reinstall the combustion system

Run this procedureArrow right

Hot Surface Igniter Testing

Check mark

Service Procedure VII — Hot Surface Igniter Testing & Replacement

Check mark

Safety Warning

Check mark

Be aware of 120-volt potential exposure and handle the igniter with caution as it may be too hot.

Check mark

Igniter Cold Resistance Check

Check mark

Check the igniter's cold resistance

Check mark

Is the igniter's cold resistance under 150 ohms?

Check mark

Replace the hot surface igniter if resistance is not under 150 ohms

Check mark

Ignition Module Voltage Check

Check mark

Check for 120VAC across the ignition module's igniter terminals during the warm-up period (igniter LED lit)

Run this procedureArrow right

Anode Rod Inspection

Check mark

Service Procedure XIV — Anode Inspection and Replacement

Check mark

Turn off the water supply and drain the water heater.

Check mark

Disassemble the heater per the Disassembly Procedure for Access to Anodes & Flue Baffles.

Check mark

Locate and remove the anode rods using a 1-1/16 in. hex socket.

Check mark

Visually inspect each anode rod for depletion or exposed steel core.

Check mark

Apply thread sealing tape or compound and reinstall the anode rods.

Check mark

Restore the water supply and check for leaks.

Check mark

Reinstall the collector cover per the Collector Cover Installation Procedure.

Check mark

Reinstall the collector insulation and control panel, reconnect the control panel wire harnesses, restore power, and verify proper operation.

Run this procedureArrow right

Unlock
efficiency with MaintainX Assist

MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Bradford White

Explore Other Assets