Bradford White Water Heater EF100T150E3N2
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Flame Sensor Testing
Service Procedure VIII — Flame Sensor Testing & Replacement
Safety Warning
Be cautious of 120-volt potential exposure and hot flame sensor
Flame Sensor Testing
Check for a minimum of 1 microamp during the 1.5-second flame-proving period
Is the flame-sensing circuit okay?
Check for expected 24VAC at ignition module/control board flame-establishing terminals
Is 24VAC present at the terminals?
Call technical support if 24VAC is absent
Anode Rod Inspection
Service Procedure XIV — Anode Inspection and Replacement
Turn off the water supply and drain the water heater
Disassemble the heater for access to anodes and flue baffles
Locate and remove the anode rods using a 1-1/16 in. hex socket
Visually inspect each anode rod for depletion
Apply thread sealing tape or compound and reinstall the anode rods
Restore the water supply and check for leaks
Reinstall the collector cover
Reinstall the collector insulation and control panel
Thermostat Circuit Testing
Service Procedure I — Thermostat Circuit Testing
Error code 32: Unplug electrical power to the water heater
Check continuity of the wire harness to the sensor
Is the resistance close to 0 ohms?
Replace the harness if resistance exceeds 0.5 ohms or wires show damage
Check sensor resistance against the temperature/resistance table
Replace the sensor if needed
Restore power and run the heater through a heating cycle
Verify proper operation by viewing sensor temperature when the burner shuts off
Burner Tube Inspection
Service Procedure III — Burner Tube Inspection & Replacement
WARNING — Heater components can be hot during this procedure; take precautions to avoid injury.
Burner Tube Removal
Turn the main power switch off and unplug the water heater, then turn off the gas supply.
Remove the surround cover, then disconnect the gas connection, PVC venting, wire harness, and silicone tubing from the gas valve.
Disconnect the wire harness from the blower assembly.
Remove the two screws holding the hot surface igniter and flame sensor and carefully remove them (for Direct Spark Ignition models, remove the spark rod bracket screws and spark rod instead).
Remove the four nuts holding the burner transition, lift the blower/gas valve/transition assembly off, and set the gasket aside.
Remove the burner tube from the burner mounting insert.
Combustion System Testing
Service Procedure II — Combustion System Testing
Observe burner operation through the sight glass
Verify minimum gas supply piping size
Confirm static inlet gas pressure is stable between 7 and 14 in. W.C.
For models with Hot Surface Ignition
Confirm the inlet gas pressure does not drop more than 2 in. W.C. during ignition
Check that the igniter glows through the sight glass during warm-up
Check for 120VAC at the ignition-module igniter terminals
Check igniter cold resistance is under 150 ohms
MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX