York Rooftop Unit ZH150E54D5B5BCA2A1
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Rooftop Unit Start-up Check
Prestart Check List
Check the electrical supply voltage being supplied
Set the room thermostat to the off position
Turn unit electrical power on
Set the room thermostat fan switch to on
Check indoor blower rotation
Check blower drive belt tension
Check the unit supply air (CFM)
Measure evaporator fan motor's amp draw
Belt Tension Adjustment
Pre-Adjustment Check
Check if the unit is equipped with additional fans
Belt Tension Adjustment Procedure
Loosen the four bolts holding the motor base to the channels
Adjust the belt by turning nuts 'A'
Apply perpendicular force to the belt using a belt tension checker
Enter the deflection distance obtained
Use the recommended deflection force per the Belt Adjustment Table
Was the belt tension checked at least two times during the first 24 hours of operation?
Supply Air Drive Adjustment
Supply Air Drive Adjustment
Pre-Adjustment Caution
Review installation for errors, leaks, or undesirable system effects
Ensure only qualified personnel make blower speed changes
Blower Speed Change Considerations
Verify understanding of fan laws
Are you aware that BHP and AMP draw increase by the cube of the blower speed?
Are you aware that static pressure increases by the square of the blower speed?
CFM Measurement and Adjustment
1 Yearly Smoke Detector Cleaning
Pre-Cleaning Inspection
Is the smoke detector securely mounted?
Check for any visible damage to the smoke detector
Cleaning Process
Turn off the power to the smoke detector
Remove the smoke detector cover
Clean the smoke detector using a vacuum or soft brush
Reattach the smoke detector cover
Turn the power back on to the smoke detector
Air Quantity Check
Method One
Remove the dot plugs from the duct panel
Insert eight inches of 1/4 inch metal tubing into the airflow on both sides of the indoor coil
Ensure tubes are perpendicular to the airflow
Determine the pressure drop across a dry evaporator coil using an Inclined Manometer or Magnehelic
Are the compressors de-energized before taking measurements?
Determine the CFM through the unit from the pressure drop indicated by the manometer
Are the air filters clean?
Adjust Measured CFM to Required CFM using SUPPLY AIR DRIVE ADJUSTMENT
Access the parts list for your equipment in MaintainX.
Optional Co2 Space Sensor Kit
2AQ04700524
Optional Co2 Sensor Kit
2AQ04700624
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Non-Plenum Application Anixter
CBL-22/3-FC-PVC
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Non-Plenum Application Belden
B5501FE
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Plenum Application Anixter
CBL-22/3-FC-PLN
Optional Co2 Space Sensor Kit
2AQ04700524
Optional Co2 Sensor Kit
2AQ04700624
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Non-Plenum Application Anixter
CBL-22/3-FC-PVC
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Non-Plenum Application Belden
B5501FE
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Plenum Application Anixter
CBL-22/3-FC-PLN
Optional Co2 Space Sensor Kit
2AQ04700524
Optional Co2 Sensor Kit
2AQ04700624
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Non-Plenum Application Anixter
CBL-22/3-FC-PVC
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Non-Plenum Application Belden
B5501FE
Fc Bus 22 Awg Stranded 3-Wire Twisted Shielded Cable Plenum Application Anixter
CBL-22/3-FC-PLN
MaintainX Assist is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX