Xylem Heat Exchanger 02014-BCF
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Heat Exchanger Storage Maintenance
Storage
Inspect for shipping damage and contamination
Is the heat exchanger placed in immediate service?
Take precautions to prevent rusting or contamination if not in immediate service
Describe preservation methods for interior surfaces during storage
Remove accumulations and prepare for indoor storage
Is the storage environment ideal?
Record storage temperature
Record relative humidity
Heat Exchanger Maintenance
Maintenance
Ensure all pressure is off equipment and the unit is drained before opening heads
Remove the bonnets
Inspect all tubes for erosion, corrosion, or foreign material
Inspect all anodes for excessive corrosion or scale insulation
Inspect filters to prevent foreign matter from entering the exchanger
Avoid blowing out heat exchangers with air when operating fluids are flammable or hazardous
Select cleaning method for heat exchangers
Use a torque wrench when replacing heads
Initial Heat Exchanger Startup Check
Operation
Open the vent connections and start to circulate the cold medium only.
Ensure that the passages in the exchanger are entirely filled with the cold fluid before closing the vents.
Introduce the hot medium gradually until all passages are filled with liquid, then close vents.
Slowly bring the unit up to temperature.
Start operation gradually without admitting hot fluid to the unit suddenly when empty or cold.
Avoid shocking the unit with cold fluid when the unit is hot.
Heat Exchanger Shutdown Maintenance
OPERATION — Shutdown
Shut off the flow of hot medium first
If circulation of cooling medium is stopped, ensure circulation of hot medium is also stopped by by-passing or otherwise
Ensure equipment is not operated under conditions in excess of those specified on nameplate
Drain all fluids to eliminate possibility of freezing and corrosion
Drain condensate from steam heaters and similar apparatus to guard against water hammer
Ensure there is no pulsation of fluids to prevent vibration and strain
Heat Exchanger Anode Inspection
Maintenance — Anodes
Verify the presence of components
Inspect anodes for scale or surface coatings
Are pipe plugs used instead of anodes?
Inspect pipe plugs for material suitability
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX