Trane Blower Coil Air Handler BCHD054B2A10A2
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
3 Monthly Equipment Check
Warning! Hazardous Service Procedures!
Acknowledge understanding of safety warnings
Safety Precautions
Disconnect all electrical power including remote disconnects
Discharge all energy storing devices such as capacitors
Follow proper lockout/tagout procedures
Is a qualified licensed electrician present for live electrical work?
Rotating Components Precautions
Disconnect all electric power, including remote disconnects
Refrigerant Coils Cleaning
WARNING: Hazardous Pressures!
Disconnect all electrical power to the unit
Wear appropriate personal protective equipment
Remove loose debris from both sides of the coil using a soft brush
Install a block-off to prevent spray from going through the coil
Mix a high-quality coil cleaning detergent with water
Place the mixed solution in a sprayer
Spray the leaving air side of the coil first, then the entering air side
Thoroughly rinse both sides of the coil and the drain pan with cool, clean water
Fan Motor Inspection
Warning! Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
Inspect fan motors for excessive vibration.
Inspect fan motors for excessive temperature.
Describe any unusual findings during the inspection.
6 Monthly Drain Pans Inspection
WARNING: Hazardous Chemicals!
Acknowledge understanding of safety precautions
Pre-Inspection Safety Measures
Wear Personal Protective Equipment (PPE)
Drain Pan and Line Inspection
Is the condensate draining as designed?
Is there evidence of standing water or condensate overflow?
Identify and remedy the cause of standing water or overflow
Drain Pan Cleaning Procedure
Fan Wheel Set Screws Check
Safety Precautions
Disconnect all electric power, including remote disconnects
Follow proper lockout/tagout procedures
Fan Wheel Set Screws Inspection
Check the fan wheel set screws for proper adjustment
Refer to Table 44 for recommendations and note any adjustments made
Access the parts list for your equipment in MaintainX.
10K NTC Thermistor
X13790374010
10K NTC Thermistor
X13790374010
10K NTC Thermistor
X13790374010
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX