Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Goodman Gas Furnace GCES960603BNAA
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Burner Visual Check
HIGH VOLTAGE WARNING
Turn the furnace on at the thermostat
Wait a few minutes for dust to settle
Check the burner flames for the following characteristics
Are the flames stable, quiet, soft and blue with slightly orange tips?
Are the flames extending directly outward from the burner ports without curling downward, floating or lifting off the ports?
2 Monthly Filter Replacement
WARNING: HIGH VOLTAGE
Disconnect all power sources before servicing
Verify power disconnection from all sources
Filter Maintenance
Is the filter permanent?
Clean the permanent filter if applicable
Replace the disposable filter if applicable
Was the filter replaced with the same type and size?
Post Maintenance
1 Yearly Furnace Inspection
WARNING: HIGH VOLTAGE
Disconnect all power before servicing or installing the unit.
Check the following furnace components for proper working order
Flue Pipe System Inspection
Check for blockage and/or leakage in the flue pipe system.
Inspect the outside termination and connections at and internal to the furnace.
Combustion Air Intake Pipe System Inspection
Check for blockage and/or leakage in the combustion air intake pipe system.
Inspect the outside termination and connection at the furnace.
Electronic Air Cleaner Inspection
Pre-Inspection Setup
Ensure the air cleaner is installed in the correct position (not with the access door facing down).
Verify the air cleaner is located in the return air duct next to the blower compartment.
Electronic Air Cleaner Inspection
Check accessibility for periodic inspection and cleaning of pre-filters and electronic cells.
Inspect and clean the pre-filters.
Inspect and clean the electronic cells.
Media Air Cleaner Inspection
Check accessibility for periodic inspection and replacement of the Media Air Cleaner filter cartridge.
Pressure Regulator Adjustment
Safety Precautions
Connect a manometer to the outlet tap at the gas valve before adjusting the pressure regulator.
Pressure Regulator Adjustment
Measure the current manifold pressure.
Is the manifold pressure within the acceptable range for natural gas (3.5 ± 3 inches water column) or propane gas (10 ± 3 inches water column)?
Adjust the pressure regulator direction
Propane Gas Specific Instructions
Ensure no unit gas valve regulator is used for propane gas.
Adjust the second stage supply line pressure regulator to 10 inches water column with all other gas consuming appliances running.
Access the parts list for your equipment in MaintainX.
Electronic Air Cleaner
GSAS
Electronic Air Cleaner
ASAS
Media Air Cleaner
GMU
Media Air Cleaner
AMU
Filter Cartridge
M0-1056
Electronic Air Cleaner
GSAS
Electronic Air Cleaner
ASAS
Media Air Cleaner
GMU
Media Air Cleaner
AMU
Filter Cartridge
M0-1056
Electronic Air Cleaner
GSAS
Electronic Air Cleaner
ASAS
Media Air Cleaner
GMU
Media Air Cleaner
AMU
Filter Cartridge
M0-1056
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX