Manual for Schneider Electric Pressure Transmitter IAP10S-V

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Schneider Electric Pressure Transmitter IAP10S-V

Schneider Electric Pressure Transmitter IAP10S-V

Create an account to install this asset package.

Maintenance Plans for Schneider Electric Pressure Transmitter Model IAP10S-V

Integrate maintenance plans directly into your work orders in MaintainX.

Pressure Transmitter Partial Proof Testing

Check mark

Preparation

Check mark

Ensure required tools are available

Check mark

Follow the required protocol to remove the device from online operation

Check mark

Testing the Milliamp Output

Check mark

Override the milliamp output to the High Failsafe setting

Check mark

Confirm the mA output corresponds to 21.0 mA

Check mark

Override the milliamp output to the Low Failsafe setting

Check mark

Confirm the mA output corresponds to 3.6 mA

Check mark

Post-Test Procedures

Run this procedureArrow right

Pressure Transmitter Pressure Calibration

Check mark

Preparation

Check mark

Ensure the transmitter is stabilized at the final operating temperature.

Check mark

Verify that the FoxCalTM feature is enabled or disabled as required.

Check mark

Pressure Calibration

Check mark

Apply pressure equal to or near the LRV and enter the pressure for the lower trim point.

Check mark

Apply pressure equal to or near the URV and enter the pressure for the upper trim point.

Check mark

Perform a single point calibration (zeroing) with a nonzero pressure input if desired.

Check mark

Post Calibration Checks

Check mark

Check if the underrange and overrange output values extend beyond 4 and 20 mA, respectively.

Run this procedureArrow right

Pressure Transmitter Zero Adjustment

Check mark

Transmitters with the Optional Display

Check mark

Unlatch the external zero button by turning it 90 degrees counterclockwise

Check mark

Relatch the external zero button by turning it 90 degrees clockwise

Check mark

Set or reset using the optional display

Check mark

Apply zero pressure to the transmitter or use a bypass valve to equalize pressure

Check mark

Press the external zero button until the display reads CAL AT0, then release

Check mark

Does the display read AT0done?

Check mark

Apply the lower range value (LRV) pressure to the transmitter

Check mark

Press and hold the external zero button until the display reads CAL LRV, then release

Run this procedureArrow right

Pressure Transmitter Time in Service Meter Calibration

Check mark

Viewing Time in Service

Check mark

View the total days the transmitter has been in service using the 1 Device Setup > 2 Calibration > Time in Service Meter menu selection.

Check mark

View the user days since the last reset using the 1 Device Setup > 2 Calibration > Reset User Days menu selection.

Check mark

Resetting User Days

Check mark

Reset the user days to zero if necessary.

Check mark

Calibration and Zeroing

Check mark

Perform a two-point calibration if FoxCalTM is enabled.

Check mark

Rezero the transmitter output once it has stabilized at the final operating temperature.

Check mark

Check the underrange and overrange output values to ensure they extend beyond 4 and 20 mA, respectively.

Run this procedureArrow right

Pressure Transmitter One-Point Calibration

Check mark

Calibration Preparation

Check mark

Select calibration method

Check mark

Is FoxCalTM enabled?

Check mark

Perform One-Point Calibration at LRV

Check mark

Perform one-point offset calibration at LRV

Check mark

Is the transmitter output stabilized at the final operating temperature?

Check mark

Rezero the transmitter output if necessary

Check mark

Post-Calibration Checks

Check mark

Check underrange and overrange output values extend beyond 4 and 20 mA

Run this procedureArrow right

Parts for Schneider Electric Pressure Transmitter IAP10S-V

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Heat Sink, 1 Inch

N1214YS

Heat Sink, 1 1/2 Inch

N1214YR

Calibration Screw Fitting

F0101ES

Silicone Lubricant

0048130

Grease, 1.75 Oz. Tube - Lubriplate For Transmitters With Aluminum Housing

X0118CC

Heat Sink, 1 Inch

N1214YS

Heat Sink, 1 1/2 Inch

N1214YR

Calibration Screw Fitting

F0101ES

Silicone Lubricant

0048130

Grease, 1.75 Oz. Tube - Lubriplate For Transmitters With Aluminum Housing

X0118CC

Heat Sink, 1 Inch

N1214YS

Heat Sink, 1 1/2 Inch

N1214YR

Calibration Screw Fitting

F0101ES

Silicone Lubricant

0048130

Grease, 1.75 Oz. Tube - Lubriplate For Transmitters With Aluminum Housing

X0118CC

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Schneider Electric

Explore Other Assets