Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Schneider Electric Circuit Breaker MTZ1-630-H3
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Circuit Breaker Visual Inspection
Record equipment identification
Check that the device is undamaged, correctly mounted, and securely fastened in the switchboard
Check the 3-phase clearance at terminal blocks
Check for debris at the back of the device housing/enclosure
Check that the ground terminals are securely connected with the correct grounding cables
Check that all external surfaces are undamaged
Rectify any non-conformities, if possible
Refer all equipment non-conformities to asset management
Remote Control Testing
Setup Connection
Connect PC running Ecoreach software using RJ45 cable to communication network
Select interface for connection
Is the control mode set to Auto: Remote?
Ecoreach Software Configuration
Select the circuit breaker in Ecoreach software
Connect to the circuit breaker
Device Operation
Access the Open and Close buttons via the Device tab
MCH Gear Motor Check
Preparation
Remove the MCH gear motor power supply
Perform an opening/closing/opening cycle to discharge the mechanism
Electrical Continuity Check
Check electrical continuity and non-continuity
Mechanism Charging
Manually charge the mechanism
Reconnect the MCH gear motor power supply
Verify the device closes and the mechanism is automatically charged
Electrical Continuity Check
Close the device
Check electrical continuity for each phase
For fixed device: Check continuity on the power terminals
For drawout device: Check continuity on the chassis power terminals with the device in the connected position
Record any anomalies found during the continuity check
Verify all tools and equipment are removed from the work area
Sign off on the completion of the procedure
Circuit Breaker Check
Condition of Connections and Auxiliaries
Check device mounting in the switchboard and the tightness of all connections
Check that all auxiliaries and accessories are correctly installed
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.