Mitsubishi Outdoor Unit MUZ-D30NA
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Cabinet Replacement
Remove the screws of the service panel
Remove the screws of the top panel
Remove the screw of the valve cover
Remove the service panel
Remove the top panel
Remove the valve cover
Remove the screws of the cabinet
Remove the cabinet
Remove the screws of the back panel
Compressor And 4-Way Valve Replacement
Remove the top panel, cabinet, service panel and the back panel.
Remove the inverter assembly.
Remove the R.V. coil.
Recover gas from the refrigerant circuit until the pressure gauge shows 0 PSIG.
Detach the brazed part of the suction and the discharge pipe connected with compressor.
Remove the compressor nuts.
Remove the compressor.
Detach the brazed part of 4-way valve and pipe.
Sign off on the compressor and 4-way valve replacement
Fan Motor Replacement
Remove the top panel, cabinet, service panel and the back panel
Disconnect the following connectors: <Electronic control P.C. board> CN931 and CN932 (Fan motor)
Remove the propeller
Remove the screws fixing the outdoor fan motor
Remove the outdoor fan motor
Inverter Assembly, P.C. Board And Power Board Replacement
Remove the top panel, cabinet, service panel and the back panel.
Disconnect the following connectors: CN931 and CN932 (Fan motor), CN795 (LEV), CN661 (Discharge temperature thermistor, defrost thermistor (MUZ) and outdoor heat exchanger temperature thermistor), CN663 (Ambient temperature thermistor), CN681 (High pressure switch) (MUZ), CN912 (4-way valve) (MUZ)
Remove the screws fixing the relay panel.
Remove the inverter assembly.
Disconnect all connectors and lead wires on the electronic control P.C. board.
Remove the electronic control P.C. board from the inverter assembly.
Remove the screws fixing the power board assembly.
Disconnect all connectors and lead wires on the power board.
Remove the power board from the inverter assembly.
Reactor Replacement
Warning: This procedure should only be performed by trained personnel.
Top panel removed
Cabinet removed
Service panel removed
Back panel removed
Reactor lead wire disconnected
Reactor screws removed
Reactor removed
Sign off on the reactor replacement
Access the parts list for your equipment in MaintainX.
Compressor
TNB220FMCHT
Compressor
TNB220FMCHT
Compressor
TNB220FMCHT
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX