Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Wilo Pump TOP-S25/13
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Thermal Insulation Shell Inspection
7.1.3 Insulation of the pump in cooling/air-conditioning systems
Verify that the two half-shells of the thermal insulation are correctly fitted
Check that the guide pins are engaged in the opposite holes
For cooling/air-conditioning systems, verify that commercially-available diffusion-proof thermal insulation materials are used instead of the supplied shells
Pump Startup Check
8 Commissioning
Check that the pump was installed and connected correctly
Ensure the sealing screw and flat gasket are in place
Prime the unit correctly
Verify that the pump rotor compartment is vented automatically
Confirm that dry running for short periods is acceptable
Ensure the motor head, differential pressure screw, and flange connection/threaded pipe union are not removed for venting
Pump Leak Check
7.1 Installation
Check for leaks after installation
Periodically verify all connections remain leak-free during operation
Ensure leakages of hazardous fluids are removed to prevent danger to persons or the environment
Rotation Direction Check
8.2 Rotation direction monitoring
Verify the following conditions for 3~ (three-phase) pumps
Briefly switch the pump on to check the direction of rotation
Is the direction of rotation correct?
Ensure the motor's direction of rotation corresponds to the direction of rotation arrow on the rating plate
If the direction of rotation is incorrect
Electrically isolate the pump
Interchange 2 phases in the terminal box
Restart the pump
Electrical Connection Check
Pre-Work Safety Measures
Ensure all poles of the power supply are disconnected before working on the pump
Wait for 5 minutes before commencing work on the module (applies only to 1~ systems)
Voltage and Connection Verification
Check that all connections (including potential-free contacts) are voltage-free
Verify that the current type and voltage of the mains connection correspond to the specifications on the rating plate
Connection and Protection Measures
Ensure the electrical connection is established via a fixed connection line with a connector device or an all-pole switch with a contact opening width of at least 3 mm
Verify mains-side fuse protection is 10 A, slow
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX