Mitsubishi Split-Type, Heat Pump Air Conditioner PUMY-SP140VKM.TH
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Accumulator Disassembling
Remove the service panel
Upload a photo of the removed service panel
Remove the top panel
Upload a photo of the removed top panel
Remove the electrical parts box
Remove the valve bed
Remove the cover panel (front)
Remove the cover panel (rear)
Remove the side panel (R)
Low Pressure Sensor and High Pressure Sensor Disassembling
Remove the service panel
Upload a photo of the removed service panel
Remove the top panel
Upload a photo of the removed top panel
Remove the side panel (R)
Disconnect the connector 63LS (blue) and the 63HS(white) on the multi controller circuit board in the electrical parts box
Loosen the clamps, which are fixing the low pressure sensor and high pressure sensor lead wire to the top of the electrical parts box
Upload a photo of the loosened clamps
Recover refrigerant
LEV Disassembling
Remove the service panel
Upload a photo of the removed service panel
Remove the top panel
Upload a photo of the removed top panel
Remove the electrical parts box
Remove the LEV coil
Recover refrigerant
Note: Recover refrigerant without spreading it in the air
Remove the welded part of LEV
TH2 and TH4 Thermistors Disassembling
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the following connectors on the controller circuit board in the electrical parts box.
•TH2: Black
•TH4:White
[Removing the thermistor <HIC> (TH2)]
(4) Loosen the fastener fixing the connector to the electrical parts box. (See Photo 10)
(5) Pull out the thermistor <HIC> (TH2) from the sensor holder. (See Photo 13)
[Removing the thermistor <Compressor> (TH4)]
High Pressure Switch Disassembling
Upload a photo of the service panel before removal
Service panel removed
Upload a photo of the top panel before removal
Top panel removed
Refer to procedure 3 for removing the electrical parts box
Electrical parts box removed
Refer to the procedure 7 (3) for removing the side panel (R)
Side panel (R) removed
2 lead wire of the high pressure switch pulled out
Access the parts list for your equipment in MaintainX.
Joint
CMY-Y62-G-E
Header
CMY-Y64/68-G-E
Joint
CMY-Y62-G-E
Header
CMY-Y64/68-G-E
Joint
CMY-Y62-G-E
Header
CMY-Y64/68-G-E
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX