Honeywell Electronic Air Cleaner F300B 20x20
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
6 Monthly Prefilters Replacement
To assure optimum performance from the air cleaner, the cells and prefilters must be cleaned regularly and the postfilters replaced regularly—twice a year with normal use or more frequently with heavy use.
Washing frequency varies, depending on the number of family members, pets, activities (such as cooking or woodworking) and smoking habits.
NOTE: To let the heating or air conditioning system operate normally while the cells are being washed, simply turn off the air cleaner switch.
Cleaning your Prefilter
1. The quickest and easiest way to clean your prefilter is to use the brush attachment of your vacuum cleaner to vacuum the lint off the dirty side of the prefilter.
Greasy dirt may require soaking the prefilter in a tub or rinsing with the garden hose. Do not wash the prefilter in the dishwasher or car wash.
2. The prefilter should be cleaned every 6 months or more frequently with heavy use. This will keep the prefilter clean of air choking lint that can make your system work harder.
Cleaning your Cells • A quick cleaning of the cells can be done by simply wiping down the ionizer wires with a damp cloth. This will help boost the efficiency of the air cleaner between full cleaning cycles. This quick clean can be done every time the prefilters are cleaned.
• A full cleaning of the cells will return the air cleaner to its peak efficiency. An easy way to wash the cells is in a tub of hot, soapy water. Just soak the cells until the water cools, agitate and rinse.
1 Yearly Air Cleaner Cleaning
Warning: This cleaning procedure requires trained personnel with PPE!
Pressure drop across the air cleaner
Pressure drop is less than 0.5 in. w.c. (0.1 kPa)?
If pressure drop is more than 0.5 in. w.c. (0.1 kPa), clean the air cleaner immediately.
Is the air cleaner installed downstream from an atomizing humidifier or does the installation include both heating and cooling?
If yes, more frequent replacement may be necessary.
Are the prefilters clogged?
If yes, clean the prefilters promptly to avoid restricting airflow and reducing efficiency of the heating-cooling system.
Record the maintenance date
6 Monthly Media Postfilters Replacement
Warning: Ensure to follow the correct procedure for replacing the media postfilters
Old filter removed successfully?
New filter available for replacement?
If new filter is not available, contact your local Honeywell distributor to purchase replacement filters
New filter installed correctly?
Sign off on the filter replacement
Reduce Ozon Odor Modification
CAUTION
Electric Shock Hazard.
Can cause personal injury.
Always disconnect power and open access door before opening power supply cover.
The electronic air cleaner generates a small amount of ozone in normal operation.
During the first week or two of operation, the amount may be higher because of sharp edges on some of the new high voltage metal parts.
Normal use quickly dulls these edges.
If desired, the ozone generated by the air cleaner can be reduced in one of two ways:
1. Install an activated carbon filter downstream from the air cleaner. Make sure particles from the air filter cannot fall into the air cleaner.
Air Cleaner Operation Check
Air cleaner switch turned on and system blower energized
Neon light next to the On-Off switch is on
Neon light goes off after system blower is turned off
Snapping sound present when test button is pushed with air cleaner energized
Steps 1 through 3 repeated for each fan speed
Sign off on the air cleaner operation check
Access the parts list for your equipment in MaintainX.
F300 Door Includes No. 2
32007528-003
Test Button Assembly
137980A
Electronic Cell
FC37A1049
Cell Handle
137266
Prefilter (Without Spring Clips)
203373
F300 Door Includes No. 2
32007528-003
Test Button Assembly
137980A
Electronic Cell
FC37A1049
Cell Handle
137266
Prefilter (Without Spring Clips)
203373
F300 Door Includes No. 2
32007528-003
Test Button Assembly
137980A
Electronic Cell
FC37A1049
Cell Handle
137266
Prefilter (Without Spring Clips)
203373
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX