Manual for Daikin Indoor Unit Wall Mounted Type Air Conditioner ATX20K2V1B

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Indoor Unit Wall Mounted Type Air Conditioner ATX20K2V1B

Daikin Indoor Unit Wall Mounted Type Air Conditioner ATX20K2V1B

Create an account to install this asset package.

Maintenance Plans for Daikin Indoor Unit Wall Mounted Type Air Conditioner Model ATX20K2V1B

Integrate maintenance plans directly into your work orders in MaintainX.

Electronic Expansion Valve Check

Check mark

EV connector correctly connected to the PCB

Check mark

EV generates a latching sound when power is turned off and on again

Check mark

Continuity confirmed when connector is disconnected and checked with a multimeter

Check mark

Check the continuity between the pins

Check mark

If there is no continuity between the pins, the EV coil is faulty

Check mark

If the continuity is confirmed, the outdoor unit PCB (main PCB) is faulty

Check mark

Sign off on the electronic expansion valve check

Run this procedureArrow right

Indoor Fan Motor Connector Output Check

Check mark

Fan motor wire breakdown / short circuit check

Check mark

1. Check the connector for connection.

Check mark

2. Turn the power off.

Check mark

3. Check if each resistance at the phases U - V and V - W is 90 Ω ~ 100 Ω (between the pins; 12 - 9, and between 9 - 6).

Check mark

Motor control voltage check

Check mark

1. Check the connector for connection.

Check mark

2. Check the motor control voltage is generated (between the pins 2 - 3).

Check mark

Rotation pulse check

Check mark

1. Check the connector for connection.

Run this procedureArrow right

Inverter Analyzer Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Power turned off?

Check mark

Install an inverter analyzer instead of a compressor

Check mark

Charged voltage of the built-in smoothing electrolytic capacitor dropped to 10 VDC or below?

Check mark

Terminals removed from the compressor?

Check mark

Terminals connected to the terminals of the inverter analyzer without touching each other?

Check mark

Activate power transistor test operation from the indoor unit

Check mark

Power turned on?

Check mark

Pressed the center of the TEMP button and the OFF button on the remote controller at the same time?

Run this procedureArrow right

Main Circuit Short Check

Check mark

Warning: Ensure the voltage between (+) and (–) of the diode bridge (DB1) is about 0 V before checking.

Check mark

Enter the voltage between (+) and (–) of the diode bridge (DB1)

Check mark

Measure the resistance between the pins of the DB1 referring to the table below.

Check mark

Enter the resistance between the pins of the DB1

Check mark

Is the resistance ∞ or less than 1 kΩ?

Check mark

If the resistance is ∞ or less than 1 kΩ, short circuit occurs on the main circuit.

Check mark

Sign off on the main circuit short check

Run this procedureArrow right

Power Module Check

Check mark

Warning: Ensure the voltage between (+) and (–) of the power module is about 0 V before proceeding

Check mark

Voltage check successful?

Check mark

Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector.

Check mark

Connector disengaged successfully?

Check mark

Measure resistance between the terminals of the power module and the terminals of the compressor with a multimeter.

Check mark

Enter the resistance measurement

Check mark

Evaluate the measurement results

Check mark

Sign off on the power module check

Run this procedureArrow right

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets