The Daikin Indoor Cooling/Heating Unit FXMQ24PVJU is a versatile HVAC solution designed for efficient climate control in residential and commercial spaces. This unit offers reliable heating and cooling performance, ensuring optimal comfort throughout the year. With advanced features and energy-efficient operation, it is an ideal choice for modern indoor environments.
Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Daikin Indoor Cooling/Heating Unit FXMQ24PVJU
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Electronic Expansion Valve Coil Check
Remove the connector for electronic expansion valve (X7A) from PCB
Check continuity between White and Yellow
Measure resistance value between White and Orange
Measure resistance value between White and Red
Measure resistance value between Yellow and Blue
Measure resistance value between Yellow and Brown
Sign off on the Electronic Expansion Valve Coil Check
Superheat Operation Check
Superheating temperature control in cooling is conducted by indoor unit electronic expansion valve
Enter the superheating temperature in cooling
Superheating temperature control in heating is conducted by outdoor unit electronic expansion valve (main)
Enter the superheating temperature in heating
Judgement criteria of superheat operation: Suction gas superheated degree: 10°C (50°F) and over. Discharge gas superheated degree: 45°C (113°F) and over, except immediately after compressor starts up or is running under drooping control
Is the suction gas superheated degree 10°C (50°F) and over?
Is the discharge gas superheated degree 45°C (113°F) and over, except immediately after compressor starts up or is running under drooping control?
Enter any additional observations or comments
Sign off on the superheat operation check
Heat Recovery System Vacuuming/Dehydration Maintenance
Choose the type of vacuuming and dehydration
Vacuum pump connected to service ports of liquid pipe and gas pipe
Enter the vacuum level achieved after 2 hours of vacuuming
Did the vacuum level reach –100.7 kPa (–14.6 psi) or less after 2 hours?
Enter the vacuum level achieved after additional 1 hour of vacuuming
Did the vacuum level reach –100.7 kPa (–14.6 psi) or less after 3 hours?
Leak tests conducted if vacuum level did not reach –100.7 kPa (–14.6 psi) or less after 3 hours?
Compressor left at the degree of vacuum of –100.7 kPa (–14.6 psi) or less for a period of 1 hour or more
Did the vacuum gauge reading rise after leaving the compressor in vacuum state for 1 hour or more?
Refrigerant Check
Refrigerant Overcharge Check
High pressure rises causing overload control
Superheated degree of suction gas lowers
Subcooled degree of condensate rises
Refrigerant Shortage Check
Superheated degree of suction gas rises causing higher compressor discharge gas temperature
Superheated degree of suction gas rises causing the electronic expansion valve to turn open
Low pressure drops causing the unit not to demonstrate cooling capacity
Sign off on the refrigerant check
Heat Recovery System Maintenance
Check for High Pressure in cooling
Check for High Pressure in heating
Check Thermistor (p. 295)
Check Pressure Sensor (p. 298)
Check for broken wire of the relay wire (p.299)
Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
Procedure for checking indoor-outdoor unit transmission wiring for broken wires
Check Fan Motor Connector (Power Supply Cable) (p.300)
Check Fan Motor Connector (Signal Cable) (p.300)
Access the parts list for your equipment in MaintainX.
Junction Pipe Kit
KHRP26A250T
Junction Pipe Kit
KHRP26A250T
Junction Pipe Kit
KHRP26A250T
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX













