MaintainX Logo
EnterprisePricing
Daikin

Daikin Indoor Cooling/Heating Unit FXMQ24PVJU

Need answers fast?
Explore the manual using AI.

Daikin Indoor Cooling/Heating Unit FXMQ24PVJU
Daikin Indoor Cooling/Heating Unit FXMQ24PVJU

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Daikin Indoor Cooling/Heating Unit FXMQ24PVJU

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Indoor Cooling/Heating Unit FXMQ24PVJU

Daikin Indoor Cooling/Heating Unit FXMQ24PVJU

Create an account to install this asset package.

Maintenance Plans for Daikin Indoor Cooling/Heating Unit Model FXMQ24PVJU

Integrate maintenance plans directly into your work orders in MaintainX.

Pressure Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Enter the compressor capacity control

Check mark

Low pressure protection control functional?

Check mark

Hot gas bypass control functional?

Check mark

Enter the superheated degree control of indoor unit electronic expansion valve

Check mark

Enter the superheated degree control of outdoor unit heat exchanger

Check mark

Sign off on the pressure check

Run this procedureArrow right

Refrigerant Check

Check mark

Refrigerant Overcharge Check

Check mark

High pressure rises causing overload control

Check mark

Superheated degree of suction gas lowers

Check mark

Subcooled degree of condensate rises

Check mark

Refrigerant Shortage Check

Check mark

Superheated degree of suction gas rises causing higher compressor discharge gas temperature

Check mark

Superheated degree of suction gas rises causing the electronic expansion valve to turn open

Check mark

Low pressure drops causing the unit not to demonstrate cooling capacity

Check mark

Sign off on the refrigerant check

Run this procedureArrow right

Heat Recovery System Vacuuming/Dehydration Maintenance

Check mark

Choose the type of vacuuming and dehydration

Check mark

Vacuum pump connected to service ports of liquid pipe and gas pipe

Check mark

Enter the vacuum level achieved after 2 hours of vacuuming

Check mark

Did the vacuum level reach –100.7 kPa (–14.6 psi) or less after 2 hours?

Check mark

Enter the vacuum level achieved after additional 1 hour of vacuuming

Check mark

Did the vacuum level reach –100.7 kPa (–14.6 psi) or less after 3 hours?

Check mark

Leak tests conducted if vacuum level did not reach –100.7 kPa (–14.6 psi) or less after 3 hours?

Check mark

Compressor left at the degree of vacuum of –100.7 kPa (–14.6 psi) or less for a period of 1 hour or more

Check mark

Did the vacuum gauge reading rise after leaving the compressor in vacuum state for 1 hour or more?

Run this procedureArrow right

Superheat Operation Check

Check mark

Superheating temperature control in cooling is conducted by indoor unit electronic expansion valve

Check mark

Enter the superheating temperature in cooling

Check mark

Superheating temperature control in heating is conducted by outdoor unit electronic expansion valve (main)

Check mark

Enter the superheating temperature in heating

Check mark

Judgement criteria of superheat operation: Suction gas superheated degree: 10°C (50°F) and over. Discharge gas superheated degree: 45°C (113°F) and over, except immediately after compressor starts up or is running under drooping control

Check mark

Is the suction gas superheated degree 10°C (50°F) and over?

Check mark

Is the discharge gas superheated degree 45°C (113°F) and over, except immediately after compressor starts up or is running under drooping control?

Check mark

Enter any additional observations or comments

Check mark

Sign off on the superheat operation check

Run this procedureArrow right

Heat Recovery System Maintenance

Check mark

Check for High Pressure in cooling

Check mark

Check for High Pressure in heating

Check mark

Check Thermistor (p. 295)

Check mark

Check Pressure Sensor (p. 298)

Check mark

Check for broken wire of the relay wire (p.299)

Check mark

Procedure for checking outdoor-outdoor unit transmission wiring for broken wires

Check mark

Procedure for checking indoor-outdoor unit transmission wiring for broken wires

Check mark

Check Fan Motor Connector (Power Supply Cable) (p.300)

Check mark

Check Fan Motor Connector (Signal Cable) (p.300)

Run this procedureArrow right

Parts for Daikin Indoor Cooling/Heating Unit FXMQ24PVJU

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Junction Pipe Kit

KHRP26A250T

Junction Pipe Kit

KHRP26A250T

Junction Pipe Kit

KHRP26A250T

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets