MaintainX Asset Hub logo
EnterprisePricing
Daikin

Daikin Condensing Unit DX13SA0483AD

Need answers fast?
Explore the manual using AI.

Daikin Condensing Unit DX13SA0483AD
Daikin Condensing Unit DX13SA0483AD

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Daikin Condensing Unit DX13SA0483AD

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Condensing Unit DX13SA0483AD

Daikin Condensing Unit DX13SA0483AD

Create an account to install this asset package.

Maintenance Plans for Daikin Condensing Unit Model DX13SA0483AD

Integrate maintenance plans directly into your work orders in MaintainX.

Voltage Check

Check mark

Warning: Line Voltage now present.

Check mark

Outer case, control panel cover, etc., removed from unit being tested

Check mark

Voltage across terminals L1 and L2 of the contactor or at the field connections for the air handler or heaters

Check mark

No reading - indicates open wiring, open fuse(s) no power or etc., from unit to fused disconnect service. Repair as needed.

Check mark

Ample voltage at line voltage connectors, unit energized

Check mark

Voltage with the unit starting and operating

Check mark

Locked Rotor Voltage

Check mark

Locked rotor voltage within the voltage tabulation as shown

Check mark

If the voltage falls below the minimum voltage, check the line wire size. Long runs of undersized wire can cause low voltage. If wire size is adequate, notify the local power company in regard to either low or high voltage.

Run this procedureArrow right

Subcooling Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Attach a photo of the thermometer or thermocouple type temperature tester attached to the liquid line

Check mark

Attach a photo of the high side pressure gauge installed on the high side service valve

Check mark

Record the gauge pressure

Check mark

Record the temperature of the line

Check mark

Enter the design subcooling obtained from the technical information manual or specification sheet

Check mark

Enter the hi-pressure reading from the 'Required Liquid Line Temperature' chart

Check mark

Enter the temperature conversion from the liquid line pressure gauge reading

Check mark

Enter the thermometer reading

Run this procedureArrow right

Fan Relay Contact Check

Check mark

WARNING: HIGH VOLTAGE! Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

Check mark

Disconnect wire leads from terminals 2 and 4 of Fan Relay Cooling and 2 and 4, 5 and 6 of Fan Relay Heating.

Check mark

Using an ohmmeter, test between 2 and 4 - should read open. Test between 5 and 6 - should read continuous.

Check mark

WARNING: Line Voltage now present.

Check mark

With power ON, energize the relays.

Check mark

Using an ohmmeter, test between 2 and 4 - should read continuous . Test between 5 and 6 - should read open.

Check mark

If not as above, replace the relay.

Check mark

Sign off on the Fan Relay Contact Check

Run this procedureArrow right

Leak Test

Check mark

WARNING: To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system.

Check mark

WARNING: To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.

Check mark

Pressure test the system using dry nitrogen and soapy water to locate leaks.

Check mark

Charge the system to 10 psi using the appropriate refrigerant

Check mark

Use nitrogen to finish charging the system to working pressure

Check mark

Apply the detector to suspect areas

Check mark

If leaks are found, repair them.

Check mark

After repair, repeat the pressure test.

Check mark

If no leaks exist, proceed to system evacuation.

Run this procedureArrow right

Compressor Check

Check mark

WARNING: Hermetic compressor electrical terminal venting can be dangerous.

Check mark

If the compressor terminal PROTECTIVE COVER and gasket (if required) are not properly in place and secured, there is a remote possibility if a terminal vents, that the vaporous and liquid discharge can be ignited, spouting flames several feet, causing potentially severe or fatal injury to anyone in its path.

Check mark

Ignition of the discharge can also occur at the venting terminal or inside the compressor, if there is sufficient contaminant air present in the system and an electrical arc occurs as the terminal vents.

Check mark

Therefore, proper evacuation of a hermetic system is essential at the time of manufacture and during servicing.

Check mark

To reduce the possibility of external ignition, all open flame, electrical power, and other heat sources should be extinguished or turned off prior to servicing a system.

Check mark

Compressor terminal PROTECTIVE COVER and gasket properly in place and secured

Check mark

Proper evacuation of a hermetic system performed

Check mark

All open flame, electrical power, and other heat sources extinguished or turned off prior to servicing

Check mark

Sign off on the compressor check

Run this procedureArrow right

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets