Bitzer Refrigeration Liquid Receiver FS152
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Initial System Vacuum Check
6.2 Evacuation
Switch on the oil heater
Open all shut-off valves and solenoid valves
Use a vacuum pump to evacuate the entire system, including the compressor, on the suction side and the high pressure side
Measure the standing vacuum achieved
Is the standing vacuum lower than 1.5 mbar?
Repeat the evacuation operation if necessary
Ensure the compressor is not started while in a vacuum
Ensure no voltage is applied to the compressor
Compressor Start-up Check
6.4 Compressor start
6.4.1 Vibrations
Check for abnormal vibrations in the system, particularly the pipelines and capillary tubes
Take additional safety measures if abnormal vibrations are detected
Ensure pipes are connected to the pressure equipment without load and stress
Receiver Leak Testing
6 Commissioning
Verify factory testing of pressure equipment
Test tightness of connections and pipe works
6.1 Testing tightness
Test refrigerant circuit for tightness according to EN378-2 or equivalent standards
Enter the overpressure applied during the test
Was dry nitrogen used for creating overpressure?
Enter the maximum allowable pressure from the name plate
Calculate and enter the test pressure (1.1-fold of the maximum allowable pressure)
Initial Refrigerant Charging Maintenance
6.3 Charging refrigerant
Ensure no components or pipes are completely charged with liquid refrigerant
Verify sufficient volume is left above the liquids
Confirm only permitted refrigerants are used
Measure out extremely precise quantities of refrigerant
Record the oil temperature
Charge the condenser or receiver directly with liquid refrigerant
Ensure blends are taken out of the charging cylinder as a bubble-free liquid
If necessary, add refrigerant while the compressor is running, charging on the suction side, preferably at the evaporator inlet
Sight Glass Cleaning
Safety Precautions
Wear safety goggles
Wear cold-protective gloves
Handling Used Oil
Pack used oil safely
Dispose of used oil in an environmentally friendly manner
Fill used oil into pressure resistant vessels
Fill vessels with nitrogen as a protective gas and close them
Mark vessels with the warning sign 'flammable substance' W021 from ISO7010
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX