York Centrifugal Chiller YKDPDPQ45CCGS
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Yearly Heat Exchangers Maintenance
7.1.6 Annually (more often if necessary)
Inspect and clean components
7.5 Condenser and Evaporator
Check for common water issues
Is water treatment necessary?
Recommendations for water treatment
7.5.1 Chemical Water Treatment
Has a chemical analysis of the water been conducted?
Water treatment expert consultation notes
Chiller Refrigerant Maintenance
7.4.4 Refrigerant Charging
Remove refrigerant charge when opening any part of the refrigerant system for repairs.
Isolate refrigerant if chiller is equipped with optional valves
Add only refrigerant vapour to the system until pressure is above freezing point of evaporator liquid.
Ensure system pressure is above 58.9 kPa for R134a at sea level.
Prevent moisture laden air from entering the system during charging.
Make up a suitable charging connection from new copper tubing.
Purge the charging connection each time a new container of refrigerant is connected.
Change containers quickly to minimise refrigerant loss.
Chiller Tube Leak Testing
Tube Leak Detection
Check for potential leak scenarios
Is refrigerant detected at the liquid head vents after shutdown?
Has system capacity and efficiency dropped sharply?
Immediate Actions for Leaks
Valve off evaporator and condenser from water circuit
Drain evaporator and condenser to prevent rusting and corrosion
Drain and purge refrigerant system with dry nitrogen
Tube Leak Testing Procedure
Initial Chiller Startup Check
5.1 Preparation
Inspect unit for installation damage
Check refrigerant charge and inspect for leaks
Check oil system charge and oil level
Verify single point of electrical isolation
Check control panel for foreign materials and cleanliness
Verify correct connection of customer power cables
Verify proper earthing of unit and tightness of internal connections
Verify site voltage supply corresponds to unit requirement
Chiller Shutdown Maintenance
6.8 Prolonged Shutdown
Test all system joints for refrigerant leaks with a leak detector
Were any refrigerant leaks found?
Repair any detected refrigerant leaks before long-term shutdown
Periodically check the tightness of the system during idle periods
Drain water from cooling tower, condenser, condenser pump, chilled water system, chilled water pump, and coils if freezing temperatures are expected
Open drains on evaporator and condenser liquid heads to ensure complete drainage
Drain water from additional systems if applicable
Disable the clock on the SETUP Screen to conserve battery
Access the parts list for your equipment in MaintainX.
Heat Conductive Compound
013-00890-000
Oil Charging Pump
070-10654
Heat Conductive Compound
013-00890-000
Oil Charging Pump
070-10654
Heat Conductive Compound
013-00890-000
Oil Charging Pump
070-10654
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX