Powrmatic Air Heater NV25-D
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Limit Thermostat Replacement
Ensure thermostats are set correctly before fitment
Verify Limit Thermostat settings
Remove screws securing the thermostat phial mounting plate to the inner bulkhead
Withdraw assembly and unclip the phial
Remove electrical connections from the limit thermostat
Remove securing nut and thermostat from the front panel
Fit replacement thermostat in reverse order
Electrode Assemblies Replacement
Disconnection and Removal
Disconnect the electrode leads from the PCB terminal
Remove the screw securing the electrode assembly to the burner assembly side plate
Withdraw the electrode assembly
Replacement and Reassembly
Fit the replacement electrode assembly
Reassemble in reverse order
Verification
Check that the spark gap is 2.5 mm
Centrifugal Fan/Motor Replacement
Disconnect the electrical connections to the centrifugal fan section
Remove the side panels of the section for access to the fan and motor
Fit replacements as appropriate and reassemble in reverse order
Check the direction of rotation for a 3-phase motor
If the direction of rotation is incorrect, interchange any two of the three phases connected to the motor
Printed Circuit Board (PCB)
Preparation
Disconnect all electrical connections
PCB Removal
Number of PCB mounting posts to release
Squeeze in the retention tag at each mounting post and release the PCB
Remove the PCB from its mounting posts
Replacement Installation
Fit replacement PCB in reverse order
Multifunctional Control Replacement
Burner Assembly Removal
Remove the burner assembly as previously described in Section 7.2
Multifunctional Control Removal
Release the flanged connections at the inlet of the multifunctional control
Release the flanged connections at the outlet of the multifunctional control
Remove the multifunctional control
New Valve Installation
Reconnect the new valve in the reverse order
Ensure the valve is correctly orientated
Access the parts list for your equipment in MaintainX.
MFC - Honeywell VR4605AB1027
145035204
MFC - Honeywell VR425AB1007
141378715
Ignition Electrode (10–75)
142423002
Rectification Electrode
142423003
Burner - Bray P51 AB 19001 (10–75)
142400240
MFC - Honeywell VR4605AB1027
145035204
MFC - Honeywell VR425AB1007
141378715
Ignition Electrode (10–75)
142423002
Rectification Electrode
142423003
Burner - Bray P51 AB 19001 (10–75)
142400240
MFC - Honeywell VR4605AB1027
145035204
MFC - Honeywell VR425AB1007
141378715
Ignition Electrode (10–75)
142423002
Rectification Electrode
142423003
Burner - Bray P51 AB 19001 (10–75)
142400240
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX