Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Greenheck Downblast Centrifugal Roof Exhaust GB-300HP
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
2000 Hourly Motor Grease Replacement
Safety Precautions
Disconnect and secure all electrical power to the fan.
Ensure the unit is non-functional by removing fuses and locking off the disconnect.
Motor Grease Replacement
Are grease fittings provided on the motor?
Is the motor temperature below 104ºF (40ºC)?
Replace the grease in accordance with the manufacturer's recommendations.
Post Maintenance Check
Ensure the following are in place after maintenance
1 Monthly Bearing Lubrication
Lubrication Frequency Assessment
Select the type of service environment
Lubrication Process
Ensure the use of a good quality lithium base grease, conforming to NLGI Grade 2 consistency
Apply grease to the bearing as per the selected service environment frequency
Post-Lubrication Check
Is the lubrication process completed without any issues?
Describe any unusual conditions or issues encountered during lubrication
1 Yearly Cast Pillow Block Bearings Lubrication
Preparation
Ensure safety precautions are in place around moving parts
Verify the use of high grade lithium base grease
Lubrication Process
Check hand gun pressure rating (maximum 40 psi)
Is the hand gun pressure within the safe range?
Rotate bearings during lubrication if safe to do so
Apply one or two shots of lubricant with a hand gun
Did a slight bead form around the seal?
Fan Belt Maintenance
Belt Inspection
Check belts for wear and tightness.
Verify belt type matches the original unit specification.
Belt Replacement
Loosen the tensioning device to allow removal of the belt by hand.
Install the new belt.
Adjust belts as shown in 'Pre‑Starting Checks.'
Pulley and Setscrew Check
Check pulley setscrews for tightness.
Initial 24 Hours Fan Belt Maintenance
Belt Tension Adjustment
Adjust belt tension after the first 24-48 hours of operation
Internal Components Inspection
Check all internal components
Belt Drive Units Inspection
Inspect belt alignment
Inspect belt tension
Adjust and tighten belt as necessary
Access the parts list for your equipment in MaintainX.
Grease(U.S. Electric Motors)
83343
Grease(U.S. Electric Motors)
83343
Grease(U.S. Electric Motors)
83343
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX