Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Daikin Air Handler CAH003GVAC
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
2000 Hours Motor Bearings Lubrication
CAUTION: Bearing overheating potential. Can damage the equipment. Do not over lubricate bearings. Use only a high grade mineral grease with a 200°F safe operating temperature.
Motor Bearings: Supply and return fans-Supply and return fan motors should have grease added after every 2000 hours of operation.
Motor is warm, but not running
Upper and lower grease plugs removed and cleaned
Grease fitting inserted into the upper hole
Clean grease added with a low pressure gun
Motor run for five minutes before replacing the plugs
NOTE: Direct-Drive Class Il fans that are supplied with TECO motors have double shielded bearings on frame sizes 140T-280T. These bearings are pre-packed with a long life grease and are not regreaseable. Larger frame size TECO motors are regreaseable and follow the same lubrication recommendations as all other motors
Select the lubricant used
Filter Maintenance
Front Load Filter Replacement
Filters removed from inside the unit
Wire clips rotated to release the prefilter and the final filter
Clean filters fully seated in the frame
Filter Gauges Cleaning
Pressure drop for installed filters
Typical filter pressure drop for clean filters at rated air flow
Final pressure drop for front loaded filters
Prefilters removed to check the pressure drop of the final filters
Fan Drive Maintenance
WARNING: Before servicing fans, lock out and tag out all power to the unit. Fans or belts can cause severe personal injury or death
WARNING: Do not open the hinged access door and screw-fastenerd access panels while the unit is operating. Moving parts and strong suction forces can cause severe personal injury or death
Adjust the fan drive
Replace the variable pitched motor sheave with a properly sized, fixed sheave
Replace the adjustable sheaves with fixed sheaves
Measure the diameter of the V-belt outer surface where it passes around the sheave (pitch diameter)
Calculate fan speed from the motor nameplate rpm
Sign off on the fan drive maintenance
1 Yearly Coil Maintenance
CAUTION: Sharp fin edges are a potential injury hazard. Avoid contact with them
Check coils for cleanliness
To obtain maximum performance, the coil must be clean
Check once a year under normal operating conditions and, if dirty, brush or vacuum clean.
Use a chemical coil cleaner on multiple row coils
Read and follow the chemical cleaner's instructions as some cleaners may contain harsh chemicals
Take care not to damage fins while cleaning.
CAUTION-Fin edges are sharp
1 Yearly Bub Replacement
WARNING: Personal Injury Hazard. Power supply can cause electrical shock. Always disconnect all power to unit before servicing
WARNING: UV-C exposure is harmful to the skin and eyes. Looking at an illuminated UV-C bulb can cause permanent blindness. UV-C skin exposure can cause cancer
WARNING: Fluorescent bulbs contain mercury, which can cause personal injury if breathed or ingested. Use appropriate protective gear to clean up broken bulbs
Verify the UV lights are off by using the view window
Disconnect power to the power receptacle before servicing
Verify the power is disconnected
Before opening the access panels, use the viewing window to make sure the UV lights are off
Before handling, allow bulbs to cool for 5 minutes
Grasp body of bulb firmly at each end
Access the parts list for your equipment in MaintainX.
Replacement Bulb
205484001
Replacement Bulb
205484101
Replacement Bulb
205484201
Replacement Bulb
205484001
Replacement Bulb
205484101
Replacement Bulb
205484201
Replacement Bulb
205484001
Replacement Bulb
205484101
Replacement Bulb
205484201
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX