Siemens Low Voltage Power Circuit Breaker WLF2A308
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Yearly Circuit Breaker Maintenance
DANGER:
Hazardous voltage.
Will cause death, serious personal injury, or equipment/property damage.
Turn off and lock out all power supplying this device before working on this device.
Only qualified personnel should work on this equipment, after becoming thoroughly familiar with all warnings, safety notices, and maintenance procedures contained herein and on the devices.
The successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance.
WARNING:
High speed moving parts.
Can cause serious personal injury.
Contact Erosion Check
It is strongly recommended that the breaker's internal contacts be inspected on a regular basis. Load breaking and short-circuit trips cause contact erosion. The WL circuit breaker is equipped with a contact erosion indicator for monitoring wear of the circuit breaker's internal contacts.
DANGER
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
WARNING
High speed moving parts.
Will cause serious personal injury.
Do not place hands or objects within the arc chamber
Current Sensor Removal
Lay circuit breaker on its side
Remove cover of cable duct
Detach connectors
Remove current sensor covers
Remove current sensors
Sign off on the current sensor removal
Arc Chute Check
It is recommended that the arc chutes be inspected on a regular basis.The arc splitter plates erode as the result of load breaking. This constitutes normal wear. The erosion of the arc splitter plates can manifest itself as wear of the plates, a layer of soot, or small spots of collections of molten metal. In case of heavy wear (severe erosion, large deposits of molten metal, etc), the circuit breaker should be replaced.
It is also necessary to replace the arc chutes when the circuit breaker's internal contacts are replaced. See Checking contact erosion (page 23-10) for evaluation of contact wear, and Replacing the circuit breaker internal contact assemblies (page 23-11) for internal contact replacement.
DANGER:
Hazardous voltage.
Will cause death, serious personal injury, or equipment damage.
Turn off and lock out all power supplying this device before working on this device.
WARNING:
High speed moving parts.
Can cause serious personal injury.
Contact Wear Indicator Adjustment
Charge the closing spring manually (refer to page 6-4)
Close the system (refer to page 6-7)
Using a screwdriver, cut the plastic indicator pin along the upper edge of the large recess. Was this successful?
Is the indicator pin still visible?
If the indicator pin is no longer visible, the contact system must be replaced.
Sign off on the contact wear indicator adjustment
Access the parts list for your equipment in MaintainX.
Circuit Breakers Secondary Disconnect Block
WLCNMD
Secondary Disconnect Extension
WLCNMDA
Screw Clamp Terminal (Sigut) System
WLGAUXPLUGP
Spring Clamp Terminal
WLGAUXPLUGT
Ring Terminal System
WLGAUXPLUGR
Circuit Breakers Secondary Disconnect Block
WLCNMD
Secondary Disconnect Extension
WLCNMDA
Screw Clamp Terminal (Sigut) System
WLGAUXPLUGP
Spring Clamp Terminal
WLGAUXPLUGT
Ring Terminal System
WLGAUXPLUGR
Circuit Breakers Secondary Disconnect Block
WLCNMD
Secondary Disconnect Extension
WLCNMDA
Screw Clamp Terminal (Sigut) System
WLGAUXPLUGP
Spring Clamp Terminal
WLGAUXPLUGT
Ring Terminal System
WLGAUXPLUGR
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX