MaintainX Logo
EnterprisePricing
Multiquip

Multiquip Portable Generator DCA300SSJU4F3

Need answers fast?
Explore the manual using AI.

Multiquip Portable Generator DCA300SSJU4F3
Multiquip Portable Generator DCA300SSJU4F3

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Multiquip Portable Generator DCA300SSJU4F3

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Multiquip Portable Generator DCA300SSJU4F3

Multiquip Portable Generator DCA300SSJU4F3

Create an account to install this asset package.

Maintenance Plans for Multiquip Portable Generator Model DCA300SSJU4F3

Integrate maintenance plans directly into your work orders in MaintainX.

Engine Overspeed Adjustment

Check mark

NOTICE: Be sure you have adjusted the engine crank disconnect potentiometer first.

Check mark

Turn the engine overspeed adjustment potentiometer (Figure 56C) 30 turns clockwise

Check mark

Using a small, flat-blade screwdriver, set the DIP switch at position 5 (Figure 56D) to the ON position (up)

Check mark

Start the engine. It should crank and start. Verify that the engine running LED is lit.

Check mark

Now start turning the overspeed adjustment potentiometer counterclockwise until the engine control shuts down the engine (overspeed fault)

Check mark

Again using a small, flat-blade screwdriver, set the DIP switch at position 5 to the OFF position (down)

Check mark

If the overcrank and overspeed LEDs light at the same time on the ECU, reference troubleshooting flow charts in this service manual for additional information.

Check mark

Sign off on the engine overspeed adjustment

Run this procedureArrow right

Mpu Adjustment

Check mark

Loosen the jam nut that secures the MPU to the sensor plate

Check mark

Remove MPU

Check mark

Visually view the flywheel teeth through the hole opening on the sensor plate

Check mark

Attach a ratchet to the crankshaft pulley and rotate the flywheel gear until the highest point of the flywheel gear tooth is visible

Check mark

Reinstall the MPU sensor back into the sensor plate. Continue screwing the MPU sensor clockwise until contact is made with the flywheel gear tooth

Check mark

After making contact with the flywheel gear tooth, unscrew the MPU sensor counterclockwise 1/2 turn

Check mark

Verify that the MPU sensor does not make contact with the flywheel by rotating the flywheel gear completely around. Flywheel should rotate freely

Check mark

The MPU sensor-flywheel gear gap should be adjusted so that the minimum voltage required is attained while the engine is in crank status. The voltage setting we are looking to obtain is 2.25 VAC +/- 0.50 VAC

Check mark

Once the correct gap is obtained, tighten the MPU sensor jam nut to secure it to the sensor plate

Run this procedureArrow right

Main Field Resistance Test

Check mark

NOTICE: Before performing the resistance test, the two black lead wires (Figure 36) must be disconnected from the rotating rectifier.

Check mark

The main field (Figure 36) consists of two black lead wires with no wire designation. These two wire leads are connected to the DC positive and DC negative terminals on the rotating rectifier in conjunction with the surge protector.

Check mark

Have the two black lead wires been disconnected from the rotating rectifier?

Check mark

Upload a photo of the disconnected wires

Check mark

Using a multimeter (Figure 36), enter the resistance across each black wire as referenced in Table 6, column B.

Check mark

Does the multimeter reading indicate an open circuit?

Check mark

If the reading indicates an open circuit, describe the component that may have to be replaced or repaired.

Check mark

Sign off on the Main Field Resistance Test

Run this procedureArrow right

Relay Base Holder Maintenance

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Fuel pump relay tested normal?

Check mark

If fuel pump relay did not test normal, report the issue to the maintenance team and stop the procedure

Check mark

Is the relay base holder a 'sealed type'?

Check mark

If the relay base holder is a 'sealed type', report the issue to the maintenance team and stop the procedure

Check mark

Cleaning of the relay base holder

Check mark

Fuel pump relay removed from its base holder?

Check mark

Dielectric cleaner sprayed onto the contact pins on the relay base holder?

Check mark

Enter the air pressure used to blow off any dirt and debris

Run this procedureArrow right

Generator Inspection

Check mark

Cable ends, wire connectors and terminals, tighten and repair as needed

Check mark

Generator end for signs of heat discoloration

Check mark

Panel controls and breakers for signs of heat discoloration and that they are securely mounted

Check mark

All gauges for proper operation during test run

Check mark

Frequency and voltage, adjust as necessary

Check mark

Sign off on the generator inspection

Run this procedureArrow right

Parts for Multiquip Portable Generator DCA300SSJU4F3

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Output Terminal Bolt

M9220100914

Tie Bolt 123.0 N.M

M9220101004

Change-Over Board Bolt

M9220101104

Output Terminal Bolt

M9220100914

Tie Bolt 123.0 N.M

M9220101004

Change-Over Board Bolt

M9220101104

Output Terminal Bolt

M9220100914

Tie Bolt 123.0 N.M

M9220101004

Change-Over Board Bolt

M9220101104

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Multiquip

Explore Other Assets