MaintainX Asset Hub logo
EnterprisePricing
Daikin

Daikin Outdoor Unit Multi-Split Type Air Conditioner 4MXS36RMVJU

Need answers fast?
Explore the manual using AI.

Daikin Outdoor Unit Multi-Split Type Air Conditioner 4MXS36RMVJU
Daikin Outdoor Unit Multi-Split Type Air Conditioner 4MXS36RMVJU

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Daikin Outdoor Unit Multi-Split Type Air Conditioner 4MXS36RMVJU

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Outdoor Unit Multi-Split Type Air Conditioner 4MXS36RMVJU

Daikin Outdoor Unit Multi-Split Type Air Conditioner 4MXS36RMVJU

Create an account to install this asset package.

Maintenance Plans for Daikin Outdoor Unit Multi-Split Type Air Conditioner Model 4MXS36RMVJU

Integrate maintenance plans directly into your work orders in MaintainX.

Rotation Pulse Check

Check mark

Outdoor fan motor

Check mark

Make sure that the voltage of 320 V is applied.

Check mark

Set operation off and power off. Disconnect the connector S70.

Check mark

Check that the voltage between the pins 4 - 7 is 320 VDC.

Check mark

Check that the control voltage between the pins 4 - 3 is 15 VDC.

Check mark

Check that the rotation command voltage between the pins 4 - 2 is 0 ~ 15 VDC.

Check mark

Keep operation off and power off. Connect the connector S70.

Check mark

Check whether 4 pulses (0 ~ 15 VDC) are input at the pins 4 - 1 when the outdoor fan motor is rotated 1 turn by hand.

Check mark

When the fuse is melted, check the outdoor fan motor for proper function.

Run this procedureArrow right

Capacitor Voltage Check

Check mark

Warning: Check the main circuit for short circuit before proceeding

Check mark

Circuit breaker is still on

Check mark

Warning: Never touch any live parts during the procedure

Check mark

Voltage between FU2 and DC–

Check mark

Voltage between FU2 and DC– is 50 V or less

Check mark

Note: Ensure firm contact between the multimeter probes and the test points

Check mark

Sign off on the capacitor voltage check

Run this procedureArrow right

Indoor Fan Motor Connector Check

Check mark

CTXG, FTXR, CTXS, FTXS, FVXS Series

Check mark

1. Check the connection of connector.

Check mark

2. Check motor power supply voltage output (pins 4 - 7).

Check mark

3. Check motor control voltage (pins 4 - 3).

Check mark

4. Check rotation command voltage output (pins 4 - 2).

Check mark

5. Check rotation pulse input (pins 4 - 1).

Check mark

FDMQ Series

Check mark

1. Turn the power supply OFF.

Check mark

2. With the fan motor connector disconnected, measure the resistance between each pin, then make sure that the resistance is more than the value mentioned in the following table.

Run this procedureArrow right

Hall IC Check

Check mark

CDXS, FDXS Series

Check mark

Check the connector connection

Check mark

With the power on, operation off, and the connector connected, check the following

Check mark

Output voltage of about 5 V between pins 1 and 3

Check mark

Generation of 3 pulses between pins 2 and 3 when the indoor fan motor is operating

Check mark

If NG in step (1) -> Defective PCB -> Replace the PCB (control PCB)

Check mark

If NG in step (2) -> Defective Hall IC -> Replace the indoor fan motor

Check mark

If OK in both steps (1) and (2) -> Replace the PCB (control PCB)

Run this procedureArrow right

Thermistor Resistance Check

Check mark

Warning: Disconnect the connectors of the thermistors from the PCB before proceeding

Check mark

Thermistors disconnected from the PCB?

Check mark

Measure the resistance of each thermistor using a multimeter

Check mark

Note: The data is for reference purpose only

Check mark

Is the room temperature thermistor soldered on a PCB?

Check mark

If yes, remove the PCB from the control PCB to measure the resistance

Check mark

Is the connector of indoor heat exchanger thermistor soldered on a PCB?

Check mark

If yes, remove the thermistor and measure the resistance

Check mark

Sign off on the thermistor resistance check

Run this procedureArrow right

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets