Manual for Daikin Indoor Unit Multi-Split Type Air Conditioner CTXG12QVJUW

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Indoor Unit Multi-Split Type Air Conditioner CTXG12QVJUW

Daikin Indoor Unit Multi-Split Type Air Conditioner CTXG12QVJUW

Create an account to install this asset package.

Maintenance Plans for Daikin Indoor Unit Multi-Split Type Air Conditioner Model CTXG12QVJUW

Integrate maintenance plans directly into your work orders in MaintainX.

Inverter Analyzer Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Is the power turned off?

Check mark

If power is not turned off, stop the procedure and turn off the power

Check mark

Is the charged voltage of the built-in smoothing electrolytic capacitor 10 VDC or below?

Check mark

If the charged voltage is above 10 VDC, wait until it drops to 10 VDC or below

Check mark

Are the terminals from the compressor removed?

Check mark

Are the terminals connected to the terminals of the inverter analyzer?

Check mark

Warning: Do not let the terminals (U,V,W) touch each other. High voltage is applied.

Check mark

Is the power transistor test operation activated from the outdoor unit?

Run this procedureArrow right

Rotation Pulse Check

Check mark

Outdoor fan motor

Check mark

Voltage between the pins 4 - 7

Check mark

Control voltage between the pins 4 - 3

Check mark

Rotation command voltage between the pins 4 - 2

Check mark

Pulses at the pins 4 - 1 when the outdoor fan motor is rotated 1 turn by hand

Check mark

Fuse melted?

Check mark

Outdoor fan motor functioning properly?

Check mark

Defective PCB?

Check mark

Defective Hall IC?

Run this procedureArrow right

Capacitor Voltage Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Main circuit checked for short circuit?

Check mark

Voltage between FU2 and DC–

Check mark

Voltage 50 V or less?

Check mark

Ensure firm contact between the multimeter probes and the test points.

Check mark

Sign off on the capacitor voltage check

Run this procedureArrow right

Power Supply Waveform Check

Check mark

Warning: This check requires trained personnel with PPE!

Check mark

Enter the power supply waveform measurement between No. 1 and No. 2 on the terminal board

Check mark

Is the power supply waveform a sine wave as shown in Fig.1?

Check mark

Is there any waveform disturbance near the zero-cross as shown in the sections circled in Fig.2?

Check mark

Upload a photo of the measured waveform

Check mark

Sign off on the power supply waveform check

Run this procedureArrow right

Power Module Check

Check mark

Warning: Ensure that the voltage between (+) and (–) of the power module is about 0 V before proceeding

Check mark

Voltage between (+) and (–) of the power module is about 0 V

Check mark

Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector.

Check mark

Compressor harness connector disconnected from the outdoor unit PCB

Check mark

Measure resistance between the (+) or (–) terminal of the power module and the U, V, or W terminal of the compressor with a multimeter.

Check mark

Enter the resistance measurement

Check mark

Evaluate the measurement results

Check mark

Sign off on the power module check

Run this procedureArrow right

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets