Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Daikin Centrifugal Compressor Water Chiller HSC076
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Yearly Motor Maintenance
Warning: Only fully qualified technicians must attempt service.
Meg. Windings
Power factory correction capacitors disconnected?
Surge capacitor disconnected?
Terminal Check (Infrared temperature measurement)
Enter the temperature reading
Motor Cooling Filter Drier Pressure Drop
Enter the pressure drop reading
Technician's signature
1 Weekly Refrigerant Leak Test
Warning: Do not use oxygen or a mixture of R-22 and air to build up pressure as an explosion can occur causing serious personal injury.
Enter the initial pressure of the system in psig
Enter the pressure after adding refrigerant in psig
Enter the pressure after adding dry nitrogen in psig
Did the electronic leak detector find any leaks?
If leaks are found in welded or brazed joints, or it is necessary to replace a gasket, relieve the test pressure in the system before proceeding.
Were any leaks found in welded or brazed joints?
Was it necessary to replace a gasket?
After making any necessary repair, the system must be evacuated as described in the following section.
Refrigerant Cycle Maintenance
Maintenance of the refrigerant cycle
Record the oil pressure
Record the suction pressure
Record the discharge pressure
Record the condenser water temperature
Record the chiller water temperature
Monthly Maintenance
Record the suction line temperature at the compressor
Calculate the suction superheat by subtracting the saturated temperature equivalent of the suction pressure from the suction line temperature
1 Yearly Lubrication System Maintenance
Clean Oil Cooler Strainer (water)
Perform Oil Analysis
Oil filter change and compressor teardown and inspection should be done based on the results of the annual oil test performed by a company specializing in this type of test.
Enter the results of the oil test
Consult Daikin Service for recommendations.
Sign off on the lubrication system maintenance
1 Monthly Suction Line Temperature Check
Refrigerant Cycle Maintenance
Maintenance of the refrigerant cycle includes maintaining a log of the operating conditions, and checking that the unit has the proper oil and refrigerant charge.
Oil pressure
Suction pressure
Discharge pressure
Condenser water temperature
Chiller water temperature
The suction line temperature at the compressor should be taken at least once a month.
Suction line temperature
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX