

Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Daikin Air Handling Unit OAH015GHAM
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Water Coils Winterizing
WARNING: Mold can cause personal injury. Clean drain pan regularly so mold does not develop.
Coils can freeze due to air stratification or failure of outdoor air dampers and/or preheat controls.
Do not depend on routine draining of water cooling coils for winter shutdown as insurance against freeze-up. Severe coil damage can result.
Drain all coils as thoroughly as possible.
Fill each coil independently with an antifreeze solution using a small circulating pump and again thoroughly drain.
Check freezing point of antifreeze before proceeding to next coil.
Due to a small amount of water always remaining in each coil, there is a diluting effect. The small amount of antifreeze solution remaining in the coil must always be concentrated enough to prevent freeze-up.
NOTE: Carefully read instructions for mixing antifreeze solution used. Some products have a higher freezing point in their natural state when mixed with water.
Daikin Applied is not responsible for the freezing of coils.
48 Hours Air Handling Unit Check
Warning: Disconnect and lock electrical power source before starting the procedure
Check tightness of all bearing, wheel, and sheave setscrews (or capscrews)
Refer to Table 28 on page 42 for more details
Recheck belt tension and adjust if necessary
Belts that are tensioned sufficiently to slip one to two seconds at startup perform satisfactorily, extending life and reducing vibration
If re-tensioning is necessary, be certain to retain sheave alignment
Sign off on the 48 Hours Air Handling Unit Check
Fan Drive Belt Adjustment
WARNING: Moving belt and fan can cause severe personal injury or death. During installation and filter maintenance: Verify that the belt and fan guards on plenum fan units are always in place. Lock and tag out fans to prevent accidental start up. Do not enter the filter compartment until the fan is completely stopped. Use approved equipment for reaching filters located above normal reach. Do not step on filter frames or unit components. Floor surfaces must be dry and free of oil or grease.
General Rules of Tensioning
The ideal tension is the lowest tension at which the belt does not slip under peak load conditions
Check tension frequently during the first 24 to 48 hours of operation
Over tensioning shortens belt and bearing life
Keep belts free from foreign material that can cause slippage
Inspect V-drive on a periodic basis
Adjust tension if the belt is slipping
Do not apply belt dressing. This can damage the belt and cause early failure
1 Yearly Electrical System Check
All electrical connections checked and snug
Signs of water damage such as corrosion inspected
Ground conductor and connection integrity checked
Service needed?
Sign off on the electrical system check
Front Load Filter Change
Warning: Ensure the unit is turned off before starting the procedure
Filters removed from inside the unit
Wire clips rotated
Prefilter and final filter released
Upload a photo of the removed filters
Clean filters installed
Filters fully seated in the frame
Upload a photo of the installed filters
Sign off on the filter change
Access the parts list for your equipment in MaintainX.
High Voltage Harness, 30 Foot Long, One Required Per Fan
910232406
Block-Off Plate, Fan Size 355, All kW
910198700
Block-Off Plate, Fan Size 450, All kW
910198701
Block-Off Plate, Fan Size 560, All kW
910311272
Block-Off Plate, Fan Size 630, 5.9 kW; 6.3 kW
910311272
High Voltage Harness, 30 Foot Long, One Required Per Fan
910232406
Block-Off Plate, Fan Size 355, All kW
910198700
Block-Off Plate, Fan Size 450, All kW
910198701
Block-Off Plate, Fan Size 560, All kW
910311272
Block-Off Plate, Fan Size 630, 5.9 kW; 6.3 kW
910311272
High Voltage Harness, 30 Foot Long, One Required Per Fan
910232406
Block-Off Plate, Fan Size 355, All kW
910198700
Block-Off Plate, Fan Size 450, All kW
910198701
Block-Off Plate, Fan Size 560, All kW
910311272
Block-Off Plate, Fan Size 630, 5.9 kW; 6.3 kW
910311272
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX













