MaintainX Asset Hub logo
EnterprisePricing
Daikin

Daikin Air Handling Unit OAH030GHAM

Need answers fast?
Explore the manual using AI.

Daikin Air Handling Unit OAH030GHAM
Daikin Air Handling Unit OAH030GHAM

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Daikin Air Handling Unit OAH030GHAM

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Air Handling Unit OAH030GHAM

Daikin Air Handling Unit OAH030GHAM

Create an account to install this asset package.

Maintenance Plans for Daikin Air Handling Unit Model OAH030GHAM

Integrate maintenance plans directly into your work orders in MaintainX.

48 Hours Air Handling Unit Check

Check mark

Disconnect and lock electrical power source

Check mark

Check tightness of all bearing, wheel, and sheave setscrews (or capscrews). Refer to Table 28 on page 42

Check mark

Recheck belt tension and adjust if necessary. Belts that are tensioned sufficiently to slip one to two seconds at startup perform satisfactorily, extending life and reducing vibration

Check mark

If re-tensioning is necessary, be certain to retain sheave alignment

Run this procedureArrow right

Fan Drive Sheaves Maintenance

Check mark

Fan Drive

Check mark

WARNING

Check mark

Before servicing lock out and tag out all power to the unit

Check mark

Fans or belts cause severe personal injury or death

Check mark

WARNING

Check mark

Do not open the hinged access door and screw-fastened access panels while the unit is operating

Check mark

Moving parts and strong suction forces can cause severe personal injury or death

Check mark

Upon completion of the air balance, replace the variable pitched motor sheave with a properly sized, fixed sheave

Check mark

A matching fixed sheave provides longer belt and bearing life and minimizes vibration

Run this procedureArrow right

Water Coils Winterizing

Check mark

WARNING: Mold can cause personal injury. Clean drain pan regularly so mold does not develop.

Check mark

Coils can freeze due to air stratification or failure of outdoor air dampers and/or preheat controls.

Check mark

Do not depend on routine draining of water cooling coils for winter shutdown as insurance against freeze-up. Severe coil damage can result.

Check mark

Drain all coils as thoroughly as possible

Check mark

Fill each coil independently with an antifreeze solution using a small circulating pump and again thoroughly drain.

Check mark

Check freezing point of antifreeze before proceeding to next coil.

Check mark

Due to a small amount of water always remaining in each coil, there is a diluting effect. The small amount of antifreeze solution remaining in the coil must always be concentrated enough to prevent freeze-up.

Check mark

NOTE: Carefully read instructions for mixing antifreeze solution used. Some products have a higher freezing point in their natural state when mixed with water.

Check mark

Daikin Applied is not responsible for the freezing of coils.

Run this procedureArrow right

Air Handling Unit Components Replacement

Check mark

Removing and Replacing Components

Check mark

WARNING

Check mark

Before removing component, lock out and tag out all power to the unit

Check mark

Fans and belts can cause severe personal injury or death

Check mark

See page 12 for instructions on removing panels and opening fan access doors to remove or replace components

Check mark

Removing the Fan Section

Check mark

The fan shaft, motor, and any drive components can be removed and replaced through the access door opening

Check mark

If required, the side panel can be removed for additional access

Check mark

If fan replacement is required, the entire fan assembly can be pulled out the side of the cabinet for housed fan assemblies

Run this procedureArrow right

Front Load Filter Change

Check mark

Warning: Ensure the unit is turned off before starting the procedure

Check mark

Filters removed from inside the unit

Check mark

Wire clips rotated

Check mark

Prefilter and final filter released

Check mark

Clean filters installed

Check mark

Filters fully seated in the frame

Check mark

Sign off on the filter change

Run this procedureArrow right

Parts for Daikin Air Handling Unit OAH030GHAM

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

High Voltage Harness, 30 Foot Long, One Required Per Fan

910232406

Block-Off Plate, Fan Size 355, All kW

910198700

Block-Off Plate, Fan Size 450, All kW

910198701

Block-Off Plate, Fan Size 560, All kW

910311272

Block-Off Plate, Fan Size 630, 5.9 kW; 6.3 kW

910311272

High Voltage Harness, 30 Foot Long, One Required Per Fan

910232406

Block-Off Plate, Fan Size 355, All kW

910198700

Block-Off Plate, Fan Size 450, All kW

910198701

Block-Off Plate, Fan Size 560, All kW

910311272

Block-Off Plate, Fan Size 630, 5.9 kW; 6.3 kW

910311272

High Voltage Harness, 30 Foot Long, One Required Per Fan

910232406

Block-Off Plate, Fan Size 355, All kW

910198700

Block-Off Plate, Fan Size 450, All kW

910198701

Block-Off Plate, Fan Size 560, All kW

910311272

Block-Off Plate, Fan Size 630, 5.9 kW; 6.3 kW

910311272

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets