Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Trane Series R™ Helical Rotary Chiller RTHCD3G3G3
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Oil Sump Level Check
Run the unit fully loaded for approximately 20 minutes.
Cycle the compressor off line.
Attach the 3/8” or 1/2” hose with a sightglass in the middle to the oil sump drain valve and the condenser service valve at the top of the condenser.
After the unit is off line for 10 minutes move the sightglass along the edge of the condenser tubesheet at the same height of the oil sump.
Enter the oil level from the bottom of the oil sump.
Is the oil level between 2” and 5”?
If the level appears to be above 8”, the oil sump is completely full. Most likely more oil resides in the rest of the system and some oil needs to be removed until the level falls between 2” and 5” in the oil sump.
If the level is below 2”, there is not enough oil in the sump. This can occur from not enough oil in the system or more likely, oil migration to the evaporator. Oil migration can occur from a low refrigerant charge, gas pump malfunction, etc.
Is the gas pump functioning properly?
1 Monthly Series R™ Helical Rotary Chiller Maintenance
Review operating log
Clean all water strainers in both the chilled and condensing water piping systems
Measure the oil filter pressure drop
Replace oil filter if required
Measure and log the subcooling and superheat
If operating conditions indicate a refrigerant shortage, leak check the unit using soap bubbles
Repair all leaks
Trim refrigerant charge until the unit operates in the conditions listed in Table 26 at full load, ARI conditions
NOTE: ARI conditions are: condenser water: 85°F and 3 GPM/XXX tons and evaporator water: 54-44°F
Compressor Oil Replacement
CAUTION: Due to the hygroscopic properties of the POE oil, all oil must be stored in metal containers. The oil will absorb water if stored in a plastic container.
Removing Compressor Oil
Is the service valve located on the bottom of the oil sump open?
Connect a line to the oil sump drain valve.
Is the line connected to the oil sump drain valve?
Open the valve and allow the desired amount of oil to flow into the container and close the charging valve.
Is the valve open and oil flowing into the container?
Measure the exact amount of oil removed from the unit.
Sign off on the compressor oil replacement
The Condenser Cleaning
CAUTION: Do not use untreated or improperly treated water, or equipment damage may occur.
Condenser tube fouling is indicated when the “approach” temperature is higher than predicted.
Standard water applications will operate with less than a 10°F approach. If the approach exceeds 10°F cleaning the condenser tubes is recommended.
NOTE: Glycol in the water system typically doubles the standard approach.
If the annual condenser tube inspection indicates that the tubes are fouled, 2 cleaning methods can be used to rid the tubes of contaminants.
Mechanical tube cleaning- this method is used to remove sludge and loose material from smoothbore condenser tubes.
Mechanical Cleaning Procedure
Remove the retaining bolts from the water boxes at each end of the condenser.
Use a hoist to lift the water boxes.
1 Weekly Series R™ Helical Rotary Chiller Maintenance
After the unit has operated for approximately 30 minutes and the system has stabilized, check the operating conditions and complete the procedures below:
Log the chiller.
Check evaporator and condenser pressures with gauges and compare to the reading on the Clear Language Display.
Pressure readings should fall within the following ranges specified in the Operating Conditions table:
NOTE: Optimum condenser pressure is dependent on condenser water temperature, and should equal the saturation pressure of the refrigerant at a temperature 2 to 5°F above that of leaving condenser water at full load.
Sign off on the weekly maintenance
Access the parts list for your equipment in MaintainX.
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX