Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Trane Series R™ Helical Rotary Chiller RTHCD2D2E2
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Refrigerant Charge
Warning: Disconnect ALL power before/during evacuation.
Cause of lost refrigerant determined and problem repaired?
Evacuation and Dehydration
Vacuum pump connected to the 5/8” flare connection on the bottom of the evaporator and/or condenser?
Enter the system pressure in microns after evacuation
Pressure below 500 microns?
Perform a standing rise test for at least an hour.
Enter the pressure rise in microns after the standing rise test
Pressure rise less than 150 microns?
3 Yearly Series R™ Helical Rotary Chiller Maintenance
Use a nondestructive tube test to inspect the condenser and evaporator tubes at 3-year intervals.
NOTE: It may be desirable to perform tube tests on these components at more frequent intervals, depending upon chiller application. This is especially true of critical process equipment.
Depending on chiller duty, contact a qualified service organization to determine when to conduct a complete examination of the unit to determine the condition of the compressor and internal components.
Nondestructive tube test passed?
Notes on the condition of the compressor and internal components
Sign off on the 3 Yearly Series R™ Helical Rotary Chiller Maintenance
The Gas Pump Oil Filter Replacement
Warning: This procedure should be performed by trained personnel only.
Gas pump returning oil to the compressor?
Enter the liquid level reading from the sensor
Enter the suction pressure reading
Enter the evaporator approach reading
Is the pressure drop across the filter within the normal range at full load conditions?
If the oil is logged in the evaporator, manually move the oil from the evaporator to the oil sump.
Sign off on the oil filter replacement
Oil Sump Level Check
Warning: This procedure requires trained personnel with PPE!
Run the unit fully loaded for approximately 20 minutes.
Cycle the compressor off line.
Attach the 3/8” or 1/2” hose with a sightglass in the middle to the oil sump drain valve and the condenser service valve at the top of the condenser.
After the unit is off line for 10 minutes move the sightglass along the edge of the condenser tubesheet at the same height of the oil sump.
Enter the oil level from the bottom of the oil sump.
If the level appears to be above 8”, the oil sump is completely full. Most likely more oil resides in the rest of the system and some oil needs to be removed until the level falls between 2” and 5” in the oil sump.
If the level is below 2”, there is not enough oil in the sump. This can occur from not enough oil in the system or more likely, oil migration to the evaporator. Oil migration can occur from a low refrigerant charge, gas pump malfunction, etc.
Confirm the operation of the gas pump.
The Main Oil Filter (Hot Filter) Replacement
Warning: This procedure requires trained personnel with PPE!
Chiller shut down on a “Low Oil Flow” diagnostic?
Compressor shut down on a “Loss of Oil at Compressor (Running) diagnostic?
Pressure drop between the two service valves in the lubrication circuit
If pressure drop exceeds the maximum level, proceed with the following steps
Isolate the oil filter by closing the two ball valves located before and after the filter.
Relieve the pressure from the hydraulic line through the 1/4” schrader valve located between the ball valve and the oil filter (or the ball valve and oil cooler, if so equipped).
Use a rubber mallet to break loose the nut that secures the oil filter element to the filter manifold.
Turn the nut clockwise until the filter element detaches from the manifold.
Access the parts list for your equipment in MaintainX.
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX