

Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Trane Series R™ Helical Rotary Chiller RTHCC2D3E3
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
The Condenser Cleaning
CAUTION: Do not use untreated or improperly treated water, or equipment damage may occur.
Condenser tube fouling is indicated when the “approach” temperature is higher than predicted.
Does the approach exceed 10°F?
If the approach exceeds 10°F cleaning the condenser tubes is recommended.
NOTE: Glycol in the water system typically doubles the standard approach.
Choose the cleaning method
Mechanical Cleaning Procedure
Remove the retaining bolts from the water boxes at each end of the condenser.
Work a round nylon- or brass- bristled brush in and out of each of the condenser water tubes to loosen the sludge.
The Gas Pump Oil Filter Replacement
Warning: This procedure should be performed by trained personnel only.
Is the gas pump returning the oil to the compressor?
Enter the pressure drop across the filter at full load conditions.
Is the pressure drop within the normal range?
If the pressure drop is not within the normal range, proceed with the filter replacement.
Upload a photo of the replaced filter.
Post-replacement, is the gas pump returning the oil to the compressor?
Sign off on the filter replacement procedure.
Refrigerant Charge
Warning: Disconnect ALL power before/during evacuation.
Is the cause of lost refrigerant determined and repaired?
Evacuation and Dehydration
Is the vacuum pump connected to the 5/8” flare connection on the bottom of the evaporator and/or condenser?
Enter the system pressure in microns after evacuation
Did the system pressure rise more than 150 microns during the standing rise test?
If the pressure rose more than 150 microns, describe the potential leak or moisture issue
Sign off on the refrigerant charge procedure
1 Weekly Series R™ Helical Rotary Chiller Maintenance
After the unit has operated for approximately 30 minutes and the system has stabilized, check the operating conditions and complete the procedures below:
Log the chiller.
Check evaporator and condenser pressures with gauges and compare to the reading on the Clear Language Display.
Pressure readings should fall within the following ranges specified in the Operating Conditions table:
NOTE: Optimum condenser pressure is dependent on condenser water temperature, and should equal the saturation pressure of the refrigerant at a temperature 2 to 5°F above that of leaving condenser water at full load.
Sign off on the weekly maintenance
Oil Sump Level Check
Run the unit fully loaded for approximately 20 minutes.
Cycle the compressor off line.
Attach the 3/8” or 1/2” hose with a sightglass in the middle to the oil sump drain valve and the condenser service valve at the top of the condenser.
After the unit is off line for 10 minutes move the sightglass along the edge of the condenser tubesheet at the same height of the oil sump.
Enter the oil level from the bottom of the oil sump.
If the level is below 2”, there is not enough oil in the sump. This can occur from not enough oil in the system or more likely, oil migration to the evaporator. Oil migration can occur from a low refrigerant charge, gas pump malfunction, etc.
If the oil is logged in the evaporator confirm the operation of the gas pump. If the gas pump is not functioning properly all oil will be logged in the evaporator.
After the level is determined, close the service valves and remove the hose/sightglass assembly.
Sign off on the oil sump level check
Access the parts list for your equipment in MaintainX.
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX













