MaintainX Logo
EnterprisePricing
Trane

Trane Series R™ Helical Rotary Chiller RTHCC1B3C2

Need answers fast?
Explore the manual using AI.

Trane Series R™ Helical Rotary Chiller RTHCC1B3C2
Trane Series R™ Helical Rotary Chiller RTHCC1B3C2

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Trane Series R™ Helical Rotary Chiller RTHCC1B3C2

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Trane Series R™ Helical Rotary Chiller RTHCC1B3C2

Trane Series R™ Helical Rotary Chiller RTHCC1B3C2

Create an account to install this asset package.

Maintenance Plans for Trane Series R™ Helical Rotary Chiller Model RTHCC1B3C2

Integrate maintenance plans directly into your work orders in MaintainX.

Compressor Oil Replacement

Check mark

CAUTION: Due to the hygroscopic properties of the POE oil, all oil must be stored in metal containers. The oil will absorb water if stored in a plastic container.

Check mark

Removing Compressor Oil

Check mark

The oil in the compressor oil sump is under a constant positive pressure at ambient temperature. To remove oil, open the service valve located on the bottom of the oil sump and drain the oil into a suitable container using the procedure outlined below:

Check mark

Connect a line to the oil sump drain valve.

Check mark

Did you open the valve and allow the desired amount of oil to flow into the container and close the charging valve?

Check mark

Measure the exact amount of oil removed from the unit.

Check mark

Sign off on the compressor oil replacement

Run this procedureArrow right

The Gas Pump Oil Filter Replacement

Check mark

Warning: This procedure should be performed by trained personnel only.

Check mark

Is the gas pump returning the oil to the compressor?

Check mark

Enter the liquid level reading from the sensor

Check mark

Enter the suction pressure reading

Check mark

Enter the evaporator approach reading

Check mark

Upload a photo of the pressure drop across the filter as shown in Figure 34

Check mark

Is the pressure drop within the normal range at full load conditions?

Check mark

If the oil is logged in the evaporator, manually move the oil from the evaporator to the oil sump.

Check mark

Sign off on the gas pump oil filter replacement

Run this procedureArrow right

Oil Sump Level Check

Check mark

Run the unit fully loaded for approximately 20 minutes.

Check mark

Cycle the compressor off line.

Check mark

Attach the 3/8” or 1/2” hose with a sightglass in the middle to the oil sump drain valve and the condenser service valve at the top of the condenser.

Check mark

After the unit is off line for 10 minutes move the sightglass along the edge of the condenser tubesheet at the same height of the oil sump.

Check mark

Enter the oil level from the bottom of the oil sump.

Check mark

If the level is below 2”, there is not enough oil in the sump. This can occur from not enough oil in the system or more likely, oil migration to the evaporator. Oil migration can occur from a low refrigerant charge, gas pump malfunction, etc.

Check mark

If the oil is logged in the evaporator confirm the operation of the gas pump. If the gas pump is not functioning properly all oil will be logged in the evaporator.

Check mark

After the level is determined, close the service valves and remove the hose/sightglass assembly.

Check mark

Sign off on the oil sump level check.

Run this procedureArrow right

1 Monthly Series R™ Helical Rotary Chiller Maintenance

Check mark

Review operating log

Check mark

Clean all water strainers in both the chilled and condensing water piping systems

Check mark

Measure the oil filter pressure drop

Check mark

Replace oil filter if required. Refer to “Service Procedures”

Check mark

Measure and log the subcooling and superheat. Refer to Table 26

Check mark

If operating conditions indicate a refrigerant shortage, leak check the unit using soap bubbles

Check mark

Repair all leaks

Check mark

Trim refrigerant charge until the unit operates in the conditions listed in Table 26 at full load, ARI conditions

Check mark

NOTE: ARI conditions are: condenser water: 85°F and 3 GPM/XXX tons and evaporator water: 54-44°F

Run this procedureArrow right

Oil Charging

Check mark

Locate the 1/4” schrader valve between the ball valve and oil filter (or the ball valve and oil cooler, if so equipped).

Check mark

Loosely connect oil pump to schrader valve called out in step 1.

Check mark

Operate oil charging pump until oil appears at the charging valve connection; then tighten the connection.

Check mark

Note: To keep air from entering the oil, the charging valve connection must be air- tight.

Check mark

Close the ball valve just upstream of the schrader valve connected to the oil pump.

Check mark

At the UCP2 display panel, press <Service Tests> and enter the password (++--++) followed by <Enter>).

Check mark

Press <enter> to access the service tools group.

Check mark

Press <next> 12 times to display “Master Oil Line Solenoid Valve: [Mode]”.

Check mark

Press ‘+’ to change the mode from “Auto” to “On”.

Run this procedureArrow right

Parts for Trane Series R™ Helical Rotary Chiller RTHCC1B3C2

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

EXV

X15110743

Chiller

6200-0079-xx

Starter

6200-0055-xx

Options

6200-0040-xx

Stepper

6200-0081-xx

EXV

X15110743

Chiller

6200-0079-xx

Starter

6200-0055-xx

Options

6200-0040-xx

Stepper

6200-0081-xx

EXV

X15110743

Chiller

6200-0079-xx

Starter

6200-0055-xx

Options

6200-0040-xx

Stepper

6200-0081-xx

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Trane

Explore Other Assets