Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Trane Series R™ Helical Rotary Chiller RTHCB1B1B1
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
The Gas Pump Oil Filter Replacement
Warning: This procedure should be performed by trained personnel only.
Gas pump able to return oil to compressor?
If gas pump is unable to return oil, proceed with filter replacement.
Enter the pressure drop across the filter at full load conditions.
Is the pressure drop within the normal range?
If pressure drop is not within the normal range, replace the filter.
Is the evaporator logged with oil?
If evaporator is logged with oil, manually move the oil from the evaporator to the oil sump.
Sign off on the gas pump oil filter replacement.
Compressor Oil Maintenance
CAUTION: To prevent oil sump heater burnout, open the unit main power disconnect switch before removing oil from the compressor.
Trane polyolester oil is the approved oil for the RTHC units. Polyolester oil is extremely hygroscopic meaning it readily attracts moisture. The oil can not be stored in plastic containers due to the hygroscopic properties. As with mineral oil, if water is in the system it will react with the oil to form acids.
Use Table 28 to determine the acceptability of the oil. The proper charge amounts are given in Table 29 .
Note: Use an oil transfer pump to change the oil regardless of chiller pressure.
Did you open the unit main power disconnect switch before removing oil from the compressor?
Did you use Trane polyolester oil for the RTHC units?
Did you store the oil in a non-plastic container?
Did you use an oil transfer pump to change the oil?
Sign off on the compressor oil maintenance
1 Weekly Series R™ Helical Rotary Chiller Maintenance
After the unit has operated for approximately 30 minutes and the system has stabilized, check the operating conditions and complete the procedures below:
Log the chiller.
Check evaporator and condenser pressures with gauges and compare to the reading on the Clear Language Display.
Pressure readings should fall within the following ranges specified in the Operating Conditions table:
NOTE: Optimum condenser pressure is dependent on condenser water temperature, and should equal the saturation pressure of the refrigerant at a temperature 2 to 5°F above that of leaving condenser water at full load.
Sign off on the weekly maintenance
1 Yearly Series R™ Helical Rotary Chiller Maintenance
WARNING: Hazardous Voltage! Disconnect all electrical power, including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death.
Perform all weekly and monthly maintenance procedures.
Check the refrigerant charge and oil level.
Routine oil changing is not necessary on a hermetic system.
Have a qualified laboratory perform an oil analysis to determine system moisture content and acid level.
IMPORTANT: Due to the hygroscopic properties of the POE oil, all oil must be stored in metal containers. The oil will absorb water if stored in a plastic container.
Check the pressure drop across the oil filter.
Contact a qualified service organization to leak check the chiller, to inspect safety controls, and inspect electrical components for deficiencies.
Inspect all piping components for leakage and damage. Clean out any inline strainers.
3 Yearly Series R™ Helical Rotary Chiller Maintenance
Use a nondestructive tube test to inspect the condenser and evaporator tubes at 3-year intervals.
NOTE: It may be desirable to perform tube tests on these components at more frequent intervals, depending upon chiller application. This is especially true of critical process equipment.
Depending on chiller duty, contact a qualified service organization to determine when to conduct a complete examination of the unit to determine the condition of the compressor and internal components.
Nondestructive tube test passed?
Describe any issues found during the tube test
Sign off on the 3-year maintenance check
Access the parts list for your equipment in MaintainX.
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
EXV
X15110743
Chiller
6200-0079-xx
Starter
6200-0055-xx
Options
6200-0040-xx
Stepper
6200-0081-xx
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX