MaintainX Logo
EnterprisePricing
Trane

Trane Series R™ Helical Rotary Chiller RTAC170S

Need answers fast?
Explore the manual using AI.

Trane Series R™ Helical Rotary Chiller RTAC170S
Trane Series R™ Helical Rotary Chiller RTAC170S

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Trane Series R™ Helical Rotary Chiller RTAC170S

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Trane Series R™ Helical Rotary Chiller RTAC170S

Trane Series R™ Helical Rotary Chiller RTAC170S

Create an account to install this asset package.

Maintenance Plans for Trane Series R™ Helical Rotary Chiller Model RTAC170S

Integrate maintenance plans directly into your work orders in MaintainX.

Inspection Checklist

Check mark

Inspect the individual pieces of the shipment for obvious damage

Check mark

Inspect the unit for concealed damage

Check mark

If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location.

Check mark

Upload photos of the damage

Check mark

Provide evidence that the damage did not occur after delivery

Check mark

Notify the carrier’s terminal of the damage immediately, by phone and by mail. Request an immediate, joint inspection of the damage with the carrier and the consignee.

Check mark

Enter the details of the carrier notified

Check mark

Notify the Trane sales representative and arrange for repair. Do not repair the unit, however, until damage is inspected by the carrier’s representative.

Check mark

Enter the details of the Trane sales representative notified

Run this procedureArrow right

Field Oil Charging

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

This procedure is used under the following circumstances: When virtually all of the oil has been removed, if the oil charge is removed from the compressor and oil system only but the unit has been run for less than 15 minutes, if the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes.

Check mark

NOTE: This procedure can be followed even with the refrigerant charge isolated in the evaporating section of the unit.

Check mark

If small quantities of oil were removed to service refrigeration components, such as the evaporator, simply replace the oil that was removed into the serviced component prior to vacuum and recharge of the refrigerant.

Check mark

If oil was removed from the compressor only to service a compressor or change the oil filter follow this procedure:

Check mark

Is the compressor a new compressor or has been removed from the system and reworked?

Check mark

Add 1 quart (2 lb.) oil to the motor cavity prior to installing the compressor into the chiller.

Check mark

Is the compressor installed in the system?

Check mark

Is the filter shut off valve closed?

Run this procedureArrow right

Clearances

Check mark

Ensure enough space around the outdoor unit for unrestricted access to all service points.

Check mark

Refer to submittal drawings for the unit dimensions.

Check mark

Enter the clearance in feet for compressor service (minimum recommended is 4 feet)

Check mark

Provide sufficient clearance for the opening of control panel doors.

Check mark

Refer to Figure 18 through Figure 19 for minimum clearances.

Check mark

Local codes requiring additional clearances will take precedence over these recommendations.

Check mark

Ensure unobstructed flow of condenser air to maintain chiller capacity and operating efficiency.

Check mark

Avoid warm air recirculation and coil starvation.

Check mark

Do not allow debris, trash, supplies etc. to accumulate in the vicinity of the unit.

Run this procedureArrow right

1 Weekly Series R™ Helical Rotary Chiller Maintenance

Check mark

While unit is running in stable conditions.

Check mark

Check MP pressure for evaporator, condenser and intermediate oil.

Check mark

Observe liquid line sight glass on EXV.

Check mark

If liquid line sight glass has bubbles measure the subcooling entering the EXV. The subcooling should never be less than 4 °F under any circumstances.

Check mark

A clear sightglass alone does not mean that the system is properly charged. Also check the rest of the system operating conditions.

Check mark

Inspect the entire system for unusual conditions and inspect the condenser coils for dirt and debris. If the coils are dirty, refer to coil cleaning.

Check mark

Sign off on the weekly maintenance

Run this procedureArrow right

High Side Charge Isolation

Check mark

Circuit is off

Check mark

Liquid line service valve is shut

Check mark

Oil return line service valve is shut

Check mark

Circuit started with the service tool (access compressor service view in Techview)

Check mark

Discharge check valve closed after unit trip

Check mark

Discharge isolation valve is closed

Check mark

Oil line shut off valve is closed

Check mark

Refrigerant remainder recovered

Check mark

NOTE: Remaining vapor can be recovered/stored in the high side of the system. Be certain to follow proper recovery procedures to avoid introduction of non-condensable gases.

Run this procedureArrow right

Parts for Trane Series R™ Helical Rotary Chiller RTAC170S

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Isolator

X10140305620

Isolator

X10140305620

Isolator

X10140305620

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Trane

Explore Other Assets