

Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Trane Series R™ Helical Rotary Chiller RTAC170S
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Inspection Checklist
Inspect the individual pieces of the shipment for obvious damage
Inspect the unit for concealed damage
If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location.
Upload photos of the damage
Provide evidence that the damage did not occur after delivery
Notify the carrier’s terminal of the damage immediately, by phone and by mail. Request an immediate, joint inspection of the damage with the carrier and the consignee.
Enter the details of the carrier notified
Notify the Trane sales representative and arrange for repair. Do not repair the unit, however, until damage is inspected by the carrier’s representative.
Enter the details of the Trane sales representative notified
Field Oil Charging
Warning: This procedure requires trained personnel with PPE!
This procedure is used under the following circumstances: When virtually all of the oil has been removed, if the oil charge is removed from the compressor and oil system only but the unit has been run for less than 15 minutes, if the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes.
NOTE: This procedure can be followed even with the refrigerant charge isolated in the evaporating section of the unit.
If small quantities of oil were removed to service refrigeration components, such as the evaporator, simply replace the oil that was removed into the serviced component prior to vacuum and recharge of the refrigerant.
If oil was removed from the compressor only to service a compressor or change the oil filter follow this procedure:
Is the compressor a new compressor or has been removed from the system and reworked?
Add 1 quart (2 lb.) oil to the motor cavity prior to installing the compressor into the chiller.
Is the compressor installed in the system?
Is the filter shut off valve closed?
Clearances
Ensure enough space around the outdoor unit for unrestricted access to all service points.
Refer to submittal drawings for the unit dimensions.
Enter the clearance in feet for compressor service (minimum recommended is 4 feet)
Provide sufficient clearance for the opening of control panel doors.
Refer to Figure 18 through Figure 19 for minimum clearances.
Local codes requiring additional clearances will take precedence over these recommendations.
Ensure unobstructed flow of condenser air to maintain chiller capacity and operating efficiency.
Avoid warm air recirculation and coil starvation.
Do not allow debris, trash, supplies etc. to accumulate in the vicinity of the unit.
1 Weekly Series R™ Helical Rotary Chiller Maintenance
While unit is running in stable conditions.
Check MP pressure for evaporator, condenser and intermediate oil.
Observe liquid line sight glass on EXV.
If liquid line sight glass has bubbles measure the subcooling entering the EXV. The subcooling should never be less than 4 °F under any circumstances.
A clear sightglass alone does not mean that the system is properly charged. Also check the rest of the system operating conditions.
Inspect the entire system for unusual conditions and inspect the condenser coils for dirt and debris. If the coils are dirty, refer to coil cleaning.
Sign off on the weekly maintenance
High Side Charge Isolation
Circuit is off
Liquid line service valve is shut
Oil return line service valve is shut
Circuit started with the service tool (access compressor service view in Techview)
Discharge check valve closed after unit trip
Discharge isolation valve is closed
Oil line shut off valve is closed
Refrigerant remainder recovered
NOTE: Remaining vapor can be recovered/stored in the high side of the system. Be certain to follow proper recovery procedures to avoid introduction of non-condensable gases.
Access the parts list for your equipment in MaintainX.
Isolator
X10140305620
Isolator
X10140305620
Isolator
X10140305620
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX













