Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Trane Series R™ Helical Rotary Chiller RTAC140S
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Low Side Charge Isolation
Circuit is off
Suction line isolation valve is closed
Oil return line service valve is closed
Liquid line service valve is closed
EXV is manually opened
Select the method used to move refrigerant from the condenser to evaporator
NOTE: If a pump is to be used, connect it before closing this valve. This port is only isolated when the valve is back seated. If a vacuum pump is used, then connect it to the discharge line service valve near the oil separator.
Evaporator is large enough to hold all the charge for any unit to below the center-line of the shell
Sign off on the Low Side Charge Isolation
Field Refrigerant Charging
CAUTION: Evaporator Damage! Water must be flowing through the evaporator during the entire charging process to avoid freezing and rupturing of the evaporator tubes. Charge first with vapor to avoid freezing tubes.
Note the weight of the amount of charge removed.
Compare the weight of the charge removed to Table 1 - Table 4. Is there a difference in charge?
A difference in charge may indicate a leak.
Attach a photo of the attached charging hose to evaporator service valve (3/8” (9mm) flare).
Is the service valve open?
Add charge to evaporator to bring total circuit charge up to the level indicated in the above chart.
Is the service valve closed?
Attach a photo of the disconnected charging hose.
Factory (initial) Oil Charging
Warning: This procedure requires trained personnel with PPE!
Is the unit new or has had all of the oil removed?
If the isolation valves is closed, then the charge may be trapped in the evaporator. In either case, the high side of the system should not be pressurized.
Is the oil line shut off valve open?
The oil charging port is a ¼” (6mm) flare fitting with a schrader valve that is on the side of the oil filter housing. This is the port that must be used to add oil into the compressor so that the filter and lines are full at the first start of the compressor.
On single or two compressor circuits?
CAUTION: Equipment Damage! Use only Trane OIL00048 in the RTAC units to avoid any catastrophic damage to the compressor or unit.
Choose the method to put oil into the unit
NOTE: The compressor filter has an internal shut off valve that will prevent oil from entering the compressor while the compressor is not running. Therefore, there is no concern about flooding the compressor with oil.
High Side Charge Isolation
Circuit is off
Liquid line service valve is shut
Oil return line service valve is shut
Circuit started with the service tool (access compressor service view in Techview)
Discharge check valve closed after unit trip
Discharge isolation valve is closed
Oil line shut off valve is closed
Refrigerant remainder recovered
NOTE: Remaining vapor can be recovered/stored in the high side of the system. Be certain to follow proper recovery procedures to avoid introduction of non-condensable gases.
Field Oil Charging
Use the initial charging procedure under the following circumstances:
• When virtually all of the oil has been removed.
• If the oil charge is removed from the compressor and oil system only but the unit has been run for less than 15 minutes.
• If the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes. However, reduce the amount of oil added to the unit by the normal quantity of oil in refrigeration system.
NOTE: This procedure can be followed even with the refrigerant charge isolated in the evaporating section of the unit. If small quantities of oil were removed to service refrigeration components, such as the evaporator, simply replace the oil that was removed into the serviced component prior to vacuum and recharge of the refrigerant.
If oil was removed from the compressor only to service a compressor or change the oil filter follow this procedure:
1. If the compressor is a new compressor or has been removed from the system and reworked, add 1 quart (2 lb.) oil to the motor cavity prior to installing the com¬pressor into the chiller.
2. Install the compressor in the system. Make sure that the filter shut off valve is closed. Other compressor isolation valves may also be closed depending upon the service that was completed. For example, changing the oil filter would require the compressor to be isolated and pulled into vacuum.
NOTE: Make sure that compressor is not pressurized.
Access the parts list for your equipment in MaintainX.
Isolator
X10140305620
Isolator
X10140305620
Isolator
X10140305620
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX