MaintainX Logo
EnterprisePricing
Trane

Trane Series R™ Helical Rotary Chiller RTAC140S

Need answers fast?
Explore the manual using AI.

Trane Series R™ Helical Rotary Chiller RTAC140S
Trane Series R™ Helical Rotary Chiller RTAC140S

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Trane Series R™ Helical Rotary Chiller RTAC140S

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Trane Series R™ Helical Rotary Chiller RTAC140S

Trane Series R™ Helical Rotary Chiller RTAC140S

Create an account to install this asset package.

Maintenance Plans for Trane Series R™ Helical Rotary Chiller Model RTAC140S

Integrate maintenance plans directly into your work orders in MaintainX.

Low Side Charge Isolation

Check mark

Circuit is off

Check mark

Suction line isolation valve is closed

Check mark

Oil return line service valve is closed

Check mark

Liquid line service valve is closed

Check mark

EXV is manually opened

Check mark

Select the method used to move refrigerant from the condenser to evaporator

Check mark

NOTE: If a pump is to be used, connect it before closing this valve. This port is only isolated when the valve is back seated. If a vacuum pump is used, then connect it to the discharge line service valve near the oil separator.

Check mark

Evaporator is large enough to hold all the charge for any unit to below the center-line of the shell

Check mark

Sign off on the Low Side Charge Isolation

Run this procedureArrow right

Field Refrigerant Charging

Check mark

CAUTION: Evaporator Damage! Water must be flowing through the evaporator during the entire charging process to avoid freezing and rupturing of the evaporator tubes. Charge first with vapor to avoid freezing tubes.

Check mark

Note the weight of the amount of charge removed.

Check mark

Compare the weight of the charge removed to Table 1 - Table 4. Is there a difference in charge?

Check mark

A difference in charge may indicate a leak.

Check mark

Attach a photo of the attached charging hose to evaporator service valve (3/8” (9mm) flare).

Check mark

Is the service valve open?

Check mark

Add charge to evaporator to bring total circuit charge up to the level indicated in the above chart.

Check mark

Is the service valve closed?

Check mark

Attach a photo of the disconnected charging hose.

Run this procedureArrow right

Factory (initial) Oil Charging

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Is the unit new or has had all of the oil removed?

Check mark

If the isolation valves is closed, then the charge may be trapped in the evaporator. In either case, the high side of the system should not be pressurized.

Check mark

Is the oil line shut off valve open?

Check mark

The oil charging port is a ¼” (6mm) flare fitting with a schrader valve that is on the side of the oil filter housing. This is the port that must be used to add oil into the compressor so that the filter and lines are full at the first start of the compressor.

Check mark

On single or two compressor circuits?

Check mark

CAUTION: Equipment Damage! Use only Trane OIL00048 in the RTAC units to avoid any catastrophic damage to the compressor or unit.

Check mark

Choose the method to put oil into the unit

Check mark

NOTE: The compressor filter has an internal shut off valve that will prevent oil from entering the compressor while the compressor is not running. Therefore, there is no concern about flooding the compressor with oil.

Run this procedureArrow right

High Side Charge Isolation

Check mark

Circuit is off

Check mark

Liquid line service valve is shut

Check mark

Oil return line service valve is shut

Check mark

Circuit started with the service tool (access compressor service view in Techview)

Check mark

Discharge check valve closed after unit trip

Check mark

Discharge isolation valve is closed

Check mark

Oil line shut off valve is closed

Check mark

Refrigerant remainder recovered

Check mark

NOTE: Remaining vapor can be recovered/stored in the high side of the system. Be certain to follow proper recovery procedures to avoid introduction of non-condensable gases.

Run this procedureArrow right

Field Oil Charging

Check mark

Use the initial charging procedure under the following circumstances:

Check mark

• When virtually all of the oil has been removed.

Check mark

• If the oil charge is removed from the compressor and oil system only but the unit has been run for less than 15 minutes.

Check mark

• If the oil charge is removed from the compressor and oil system only and the unit has been run for more than 15 minutes. However, reduce the amount of oil added to the unit by the normal quantity of oil in refrigeration system.

Check mark

NOTE: This procedure can be followed even with the refrigerant charge isolated in the evaporating section of the unit. If small quantities of oil were removed to service refrigeration components, such as the evaporator, simply replace the oil that was removed into the serviced component prior to vacuum and recharge of the refrigerant.

Check mark

If oil was removed from the compressor only to service a compressor or change the oil filter follow this procedure:

Check mark

1. If the compressor is a new compressor or has been removed from the system and reworked, add 1 quart (2 lb.) oil to the motor cavity prior to installing the com¬pressor into the chiller.

Check mark

2. Install the compressor in the system. Make sure that the filter shut off valve is closed. Other compressor isolation valves may also be closed depending upon the service that was completed. For example, changing the oil filter would require the compressor to be isolated and pulled into vacuum.

Check mark

NOTE: Make sure that compressor is not pressurized.

Run this procedureArrow right

Parts for Trane Series R™ Helical Rotary Chiller RTAC140S

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Isolator

X10140305620

Isolator

X10140305620

Isolator

X10140305620

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Trane

Explore Other Assets