

Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Trane Series R™ Helical Rotary Chiller RTAC140H
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Low Side Charge Isolation
Circuit is off
Suction line isolation valve is closed
Oil return line service valve is closed
Liquid line service valve is closed
EXV is manually opened
Select the method used to move refrigerant from the condenser to evaporator
NOTE: If a pump is to be used, connect it before closing this valve. This port is only isolated when the valve is back seated. If a vacuum pump is used, then connect it to the discharge line service valve near the oil separator.
Evaporator is large enough to hold all the charge for any unit to below the center-line of the shell
Sign off on the Low Side Charge Isolation
High Side Charge Isolation
Circuit is off
Liquid line service valve is shut
Oil return line service valve is shut
Circuit started with the service tool (access compressor service view in Techview)
Discharge check valve closed after unit trip
Discharge isolation valve is closed
Oil line shut off valve is closed
Refrigerant remainder recovered
NOTE: Remaining vapor can be recovered/stored in the high side of the system. Be certain to follow proper recovery procedures to avoid introduction of non-condensable gases.
Compressor Replacement
Isolate the refrigerant charge outside of the compressor and close all four valves leading to the compressor?
Disconnect power to the chiller. Remove the electrical junction box cover and disconnect the wires?
WARNING: Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Evacuate the compressor through the service fitting provided. If the unit does not have suction service valves, this will include evacuating the low side of the system as well?
Disconnect all four lines attached to the compressor, as well as the junction box. Remove three screws from the bottom of the compressor?
Remove the compressor by sliding it out of the chiller onto a well supported skid or other platform. The compressor is very heavy, so insure that the support is sturdy. A piece of 1x4 lumber placed between the isolators works well to support the compressor feet as it is pulled from the chiller?
Install the new compressor. Reinstall all lines, wires, and screws. Open the service valves, and trim charge as required?
Sign off on the compressor replacement
Inspection Checklist
Inspect the individual pieces of the shipment for obvious damage
Inspect the unit for concealed damage
If concealed damage is discovered, stop unpacking the shipment.
Upload photos of the damage
Provide evidence that the damage did not occur after delivery
Notify the carrier’s terminal of the damage immediately, by phone and by mail
Notify the Trane sales representative and arrange for repair
Do not repair the unit until damage is inspected by the carrier’s representative.
Sign off on the inspection checklist
Clearances
Ensure enough space around the outdoor unit for unrestricted access to all service points.
Enter the distance in feet around the outdoor unit
Is there sufficient clearance for the opening of control panel doors?
Ensure unobstructed flow of condenser air to maintain chiller capacity and operating efficiency.
Is there sufficient flow of air across the condenser heat transfer surface?
Avoid warm air recirculation and coil starvation.
Is there any warm air recirculation?
Is there any coil starvation?
Ensure no debris, trash, supplies etc. accumulate in the vicinity of the unit.
Access the parts list for your equipment in MaintainX.
Isolator
X10140305620
Isolator
X10140305620
Isolator
X10140305620
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX













