Trane CenTraVac™ Water-Cooled Chiller CVHF - 300-500 - 379 - 050S / 080S

The Trane CenTraVac™ Water-Cooled Chiller CVHF model offers efficient cooling solutions for industrial applications. With a capacity range of 300-500 tons, this chiller is designed for reliability and performance, ensuring optimal operation in various environments. Regular maintenance is essential for longevity and efficiency.

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Trane CenTraVac™ Water-Cooled Chiller CVHF - 300-500 - 379 - 050S / 080S

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Trane CenTraVac™ Water-Cooled Chiller CVHF - 300-500 - 379 - 050S / 080S

Trane CenTraVac™ Water-Cooled Chiller CVHF - 300-500 - 379 - 050S / 080S

Create an account to install this asset package.

Maintenance Plans for Trane CenTraVac™ Water-Cooled Chiller Model CVHF - 300-500 - 379 - 050S / 080S

Integrate maintenance plans directly into your work orders in MaintainX.

1 Daily Chiller Maintenance

Check mark

Chiller's evaporator pressure

Check mark

Chiller's condenser pressure

Check mark

Oil tank pressure

Check mark

Differential oil pressure

Check mark

Discharge oil pressure

Check mark

Are the readings within the values provided in the general maintenance?

Check mark

Is the oil level visible in the lower sight glass when the unit is operating?

Check mark

Sign off on the daily chiller maintenance

Run this procedureArrow right

3 Yearly Tubes Maintenance

Check mark

Use a non-destructive tube test to inspect the condenser and evaporator tubes

Check mark

Tube test performed on condenser?

Check mark

Tube test performed on evaporator?

Check mark

It may be desirable to perform tube tests on these components at more frequent intervals depending upon chiller application

Check mark

This is especially true of critical process equipment

Check mark

Ask your Sales account manager for a copy of engineering bulletin (CTV-PRB024*-EN) for clarification of the role of eddy current testing in chiller maintenance by providing information about eddy current technology and heat exchanger tubing

Check mark

Sign off on the tube maintenance

Run this procedureArrow right

1 Yearly Chiller Leak Test

Check mark

WARNING: Explosion Hazard! Never use an open flame to detect gas leaks. Use a leak test solution for leak testing.

Check mark

WARNING: Hazardous Pressures! If a heat source is required to raise the tank pressure during removal of refrigerant from cylinders, use only warm water or heat blankets to raise the tank temperature. Do not exceed a temperature of 150°F. Do not under any circumstances apply direct flame to any portion of the cylinder.

Check mark

Important: If leak testing is required, contact a Trane Service Agency;

Check mark

Shut down the chiller

Check mark

Check purge times and unit performance logs

Check mark

Review oil analysis

Check mark

Submit refrigerant sample for analysis if required

Check mark

Inspect unit for any signs of refrigerant or oil leakage

Check mark

Check unit for any loose screws on flange, volutes, or casing

Run this procedureArrow right

3 Yearly Evaporator Maintenance

Check mark

Clean Evaporator

Check mark

Is the evaporator part of a closed circuit?

Check mark

If the evaporator is part of a closed circuit, it may not accumulate appreciable amounts of scale or sludge.

Check mark

Has it been three years since the last cleaning?

Check mark

Normally, cleaning every three years is sufficient.

Check mark

Is the evaporator part of an open system, such as air washers?

Check mark

However, periodic inspection and cleaning is recommended on open evaporator systems, such as air washers.

Check mark

Sign off on the evaporator maintenance

Run this procedureArrow right

1 Yearly Chiller Maintenance

Check mark

Annual Maintenance Procedures

Check mark

Select the type of chiller

Check mark

Evaporator refrigerant temperature sensor (4R10) reading

Check mark

Is the sensor reading within the normal operating range (0°F to 90°F [-17.8°C to 32.2°C])?

Check mark

Are the condenser tubes clean?

Check mark

Are the ifm efector® flow detection sensors clean?

Check mark

Upload a photo of the compressor oil sample sent to the Trane-qualified laboratory

Check mark

Compressor motor winding resistance to ground

Check mark

Did the chiller pass the leak-test?

Run this procedureArrow right

Parts for Trane CenTraVac™ Water-Cooled Chiller CVHF - 300-500 - 379 - 050S / 080S

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Safety Hoist Ring 1/2-13, CTV Unit

RNG01885

Safety Hoist Ring 3/4-10, CTV Unit

RNG01884

Evap Lifting Fixture, CTV Unit

BAR00400

Safety Hoist Ring 1/2-13, CTV Unit

RNG01885

Safety Hoist Ring 3/4-10, CTV Unit

RNG01884

Evap Lifting Fixture, CTV Unit

BAR00400

Safety Hoist Ring 1/2-13, CTV Unit

RNG01885

Safety Hoist Ring 3/4-10, CTV Unit

RNG01884

Evap Lifting Fixture, CTV Unit

BAR00400

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Trane

Explore Other Assets