Trane CenTraVac™ Water-Cooled Chiller CVHF - 300-500 - 379 - 050S / 050L
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Yearly Chiller Maintenance
Annual Maintenance Procedures
Select the type of chiller
Enter the reading of the evaporator refrigerant temperature sensor (4R10)
Is the sensor reading within the normal operating range (0°F to 90°F [-17.8°C to 32.2°C])?
Are the condenser tubes fouled?
If fouled, clean the condenser tubes
Are the ifm efector® flow detection sensors clean?
If not clean, use Scotch-Brite® or other non-abrasive material to clean scale; do NOT use steel wool, which could cause the probe to rust
Upload the comprehensive analysis report of the compressor oil from a Trane-qualified laboratory
General Chiller Maintenance
Check chiller for normal operation
Condenser pressure
Normal pressure readings for ASME condenser
Oil tank pressure
Discharge oil pressure
Approximate Evaporator Pressure
Approximate Condenser: Pressure(a) , (b)
Oil Sump Temperature Unit not running
Oil Sump Temperature Unit running
1 Yearly Condenser Cleaning
NOTICE: Proper Water Treatment Required! The use of untreated or improperly treated water could result in scaling, erosion, corrosion, algae or slime. Use the services of a qualified water treatment specialist to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water.
Condenser tube fouling is indicated when the approach temperature (the difference between the condensing refrigerant temperature and the leaving condenser water temperature) is higher than predicted.
If the annual condenser tube inspection indicates that the tubes are fouled, two cleaning methods— mechanical and chemical—can be used to rid the tubes of contaminants. Use the mechanical cleaning method to remove sludge and loose material from smooth-bore tubes.
To clean other types of tubes including internally- enhanced types, consult a qualified service organization for recommendations.
Waterbox covers removed?
Round nylon or brass bristled brush worked in and out of each of the condenser water tubes to loosen the sludge?
Condenser water tubes thoroughly flushed with clean water?
Scale deposits are best removed by chemical means. Be sure to consult any qualified chemical house in the area (one familiar with the local water supply’s chemical mineral content) for a recommended cleaning solution suitable for the job.
NOTICE: Unit Corrosion Damage! Failure to follow instructions below could result in corrosion damage to the unit and tubes. Follow proper procedures when using corrosive chemicals to clean water side of unit. If unsure, it is recommended that the services of a qualified chemical cleaning firm be used.
1 Yearly Exterior Parts Maintenance
Chiller shut down?
Inlet guide vane linkage check
Clean and touch-up painted surfaces as needed
Repair deteriorated, torn, or missing insulation
Sign off on the exterior parts maintenance
1 Yearly Condenser Inspection
- Shut down the chiller once each year to check the items of Condenser
1. Inspect for fouling and scaling in tubes
2. Check operation of condenser water flow sensing device
3. Factory recommendation to eddy current test tubes every three years;
Access the parts list for your equipment in MaintainX.
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.