MaintainX Logo
EnterprisePricing
Trane

Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L

Need answers fast?
Explore the manual using AI.

Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L
Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L

Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L

Create an account to install this asset package.

Maintenance Plans for Trane CenTraVac™ Water-Cooled Chiller Model CVHF - 1070-1300 - 1062 - 142E / 142L

Integrate maintenance plans directly into your work orders in MaintainX.

1 Yearly Condenser Cleaning

Check mark

- Clean condenser tubes

Check mark

NOTICE

Check mark

Proper Water Treatment Required! The use of untreated or improperly treated water could result in scaling, erosion, corrosion, algae or slime

Check mark

Use the services of a qualified water treatment specialist to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water

Check mark

Condenser tube fouling is indicated when the approach temperature (the difference between the condensing refrigerant temperature and the leaving condenser water temperature) is higher than predicted

Check mark

If the annual condenser tube inspection indicates that the tubes are fouled, two cleaning methods— mechanical and chemical—can be used to rid the tubes of contaminants. Use the mechanical cleaning method to remove sludge and loose material from smooth-bore tubes

Check mark

To clean other types of tubes including internally- enhanced types, consult a qualified service organization for recommendations

Check mark

1. Follow all instructions in “Waterbox Removal and Installation,” to remove waterbox covers

Check mark

2. Work a round nylon or brass bristled brush (attached to a rod) in and out of each of the condenser water tubes to loosen the sludge

Run this procedureArrow right

1 Yearly Exterior Parts Maintenance

Check mark

- Shut down the chiller once each year to check the items of Exterior

Check mark

1. Inlet guide vane linkage

Check mark

2. Clean and touch-up painted surfaces as needed

Check mark

3. Repair deteriorated, torn, or missing insulation;

Run this procedureArrow right

2 Monthly Sacrificial Anodes Replacement

Check mark

- The replacement schedule for the optional zinc or magnesium anodes can vary greatly with the aggressiveness of the water that is in the system

Check mark

- Some sites could require anode replacement every two to three months while other sites may require anode replacement every two to three years

Check mark

1. Trane recommends inspection of anodes for wear sometime within the first several months of the anodes being placed into service

Check mark

2. If the observed loss of anode material is small, then the interval between subsequent inspections can be lengthened

Check mark

3. Replace the anode and/ or shorten the inspection interval if the anode has lost 50 percent or more of its original mass

Check mark

4. If anode depletion occurs very quickly, consult a water treatment specialist to determine if the anode material selected is correct for the application

Check mark

NOTICE

Check mark

Equipment Damage!

Check mark

Failure to follow instructions could result in equipment damage

Run this procedureArrow right

3 Yearly Tubes Maintenance

Check mark

- Use a non-destructive tube test to inspect the condenser and evaporator tubes

Check mark

1. It may be desirable to perform tube tests on these components at more frequent intervals depending upon chiller application

Check mark

2. This is especially true of critical process equipment

Check mark

3. Ask your Sales account manager for a copy of engineering bulletin (CTV-PRB024*-EN) for clarification of the role of eddy current testing in chiller maintenance by providing information about eddy current technology and heat exchanger tubing;

Run this procedureArrow right

1 Yearly Chiller Leak Test

Check mark

- Shut down the chiller once each year to check the items for Leak Test Chiller

Check mark

1. Check purge times and unit performance logs. If warranted, pressure leak test

Check mark

2. Review oil analysis. If required, submit refrigerant sample for analysis

Check mark

3. Inspect unit for any signs of refrigerant or oil leakage

Check mark

4. Check unit for any loose screws on flange, volutes, or casing

Check mark

WARNING

Check mark

Explosion Hazard!

Check mark

Failure to follow safe leak test procedures below could result in death or serious injury or equipment or property-only-damage

Check mark

Never use an open flame to detect gas leaks. Use a leak test solution for leak testing

Run this procedureArrow right

Parts for Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 142E / 142L

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

Safety Hoist Ring 3/4-10, CTV Unit

RNG01884

Safety Hoist Ring 1/2-13, CTV Unit

RNG01885

Evap Lifting Fixture, CTV Unit

BAR00400

Safety Hoist Ring 3/4-10, CTV Unit

RNG01884

Safety Hoist Ring 1/2-13, CTV Unit

RNG01885

Evap Lifting Fixture, CTV Unit

BAR00400

Safety Hoist Ring 3/4-10, CTV Unit

RNG01884

Safety Hoist Ring 1/2-13, CTV Unit

RNG01885

Evap Lifting Fixture, CTV Unit

BAR00400

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.