Patterson-Kelley Boiler N700 Sealed Combustion
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Monthly Boiler Maintenance
Test flame detection by voltage reading at the control programmer
Test high-limit control
Test operating temperature controls
Check flue gas temperature at outlet
Test the water flow switch
Test low gas pressure switch (and high gas pressure switch if supplied)
Inspect and clean the air inlet screen of any accumulated dust or lint
Installation and service must be performed by a qualified installer or service agency
6 Monthly Boiler Maintenance
Burner Maintenance
Clean burner of any accumulated dust or lint
Inspect burner for signs of deterioration or corrosion
Replace burner if deterioration or corrosion is evident
General Guidelines
Ensure installation and service are performed by a qualified installer or service agency trained on the Harsco Industrial, Patterson-Kelley P-K THERMIFIC® boiler
Verify that the blower motor does not require lubrication
1 Weekly Boiler Maintenance
Flame Observation
Is the pilot flame blue?
Is the main flame blue?
Describe any abnormalities in the flame, such as yellow color or pulsation
Air Adjustment and Combustion Check
Does the combustion appear to need adjustment?
Enter the CO2 or O2 levels from the analyzer
Compare the CO2 or O2 levels to the fire test sticker values and note any discrepancies
Corrective Actions
Burner Cleaning
Lockout and tagout gas supply to the boiler
Lockout and tagout electrical power to the boiler
Remove the top cover of the boiler
Disconnect the electrode wire
Disconnect the UV scanner
Remove mixer core
Disconnect the union in the line at the burner
Disconnect pilot and vent line, being careful not to disturb position of pilot
Loosen and remove the four burner hold-down nuts
1 Yearly Boiler Maintenance
Test flame detection by voltage reading at the control programmer
Test high-limit control
Test operating temperature controls
Check flue gas temperature at outlet
Test the water flow switch
Test low gas pressure switch (and high gas pressure switch if supplied)
Blower Fan and Burner Maintenance
Inspect and clean blower fan and inlet screen of any accumulated dust or lint
Check burner and clean off any soot or foreign material
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX