Daikin Water Chiller WSC087-BAABC
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Monthly Condenser Temperature Approach Maintenance
Warning: This maintenance check requires trained personnel with PPE!
Enter the leaving water temperature
Enter the saturated refrigerant temperature
Calculate the approach temperature (subtract saturated refrigerant temperature from leaving water temperature)
Note: Daikin's high efficiency heat exchangers have very low design approach temperatures, in the order of one to one and one half degrees F.
Is the approach temperature within the normal range?
If not, excessive tube fouling could be present.
Enter the condenser pressure drop
Is the condenser pressure drop within the normal range?
1 Monthly Evaporator Temperature Approach Maintenance
Warning: This procedure requires trained personnel with PPE!
Enter the leaving water temperature
Enter the saturated refrigerant temperature
Calculate the approach temperature (subtract saturated refrigerant temperature from leaving water temperature)
Note: Daikin's high efficiency heat exchangers have very low design approach temperatures, in the order of one to one and one half degrees F.
Is the approach temperature within the normal range?
If not, excessive tube fouling could be present.
Enter the condenser pressure drop
Enter the motor current
1 Monthly Suction Line Temperature Check
Refrigerant Cycle Maintenance
Maintain a log of the operating conditions, and check that the unit has the proper oil and refrigerant charge.
Record the oil, suction, and discharge pressures
Record the condenser and chiller water temperatures
Record the suction line temperature at the compressor
Calculate the suction superheat by subtracting the saturated temperature equivalent of the suction pressure from the suction line temperature.
Note any extreme changes in subcooling and/or superheat over a period of time. These may indicate losses of refrigerant or possible deterioration or malfunction of the expansion valves.
Proper superheat setting is 0 to 1 degree F (0.5 degree C) at full load. Such a small temperature difference can be difficult to measure accurately.
Another method is to measure the compressor discharge superheat, the difference between the actual discharge temperature and the saturated discharge temperature.
1 Weekly Refrigerant Leak Test
Warning: Do not use oxygen or a mixture of R-22 and air to build up pressure as an explosion can occur causing serious personal injury.
Loss of the entire refrigerant charge?
Enter the pressure after charging refrigerant (psig)
Enter the pressure after adding dry nitrogen (psig)
Leak test with an electronic leak detector passed?
Water flow through the vessels maintained?
Any leaks found in welded or brazed joints?
Necessary to replace a gasket?
If any leaks are found in welded or brazed joints, or it is necessary to replace a gasket, relieve the test pressure in the system before proceeding. Brazing is required for copper joints.
1 Yearly Chiller Shutdown
Seasonal Servicing
Is the chiller subject to freezing temperatures?
If yes, drain the condenser and chiller of all water.
Use dry air to force all water out of the condenser.
Remove condenser heads.
Blow out the tubes of the condenser and evaporator.
Circulate antifreeze through the water circuits to avoid freeze up.
Have measures been taken to prevent the shutoff valve in the water supply line from being accidentally turned on?
If a cooling tower is used, has the water pump been exposed to freezing temperatures?
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX