MaintainX Asset Hub logo
EnterprisePricing
Daikin

Daikin Outdoor Unit Multi-Split Type Air Conditioner 3MXS24RMVJUA

Need answers fast?
Explore the manual using AI.

Daikin Outdoor Unit Multi-Split Type Air Conditioner 3MXS24RMVJUA
Daikin Outdoor Unit Multi-Split Type Air Conditioner 3MXS24RMVJUA

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Daikin Outdoor Unit Multi-Split Type Air Conditioner 3MXS24RMVJUA

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Outdoor Unit Multi-Split Type Air Conditioner 3MXS24RMVJUA

Daikin Outdoor Unit Multi-Split Type Air Conditioner 3MXS24RMVJUA

Create an account to install this asset package.

Maintenance Plans for Daikin Outdoor Unit Multi-Split Type Air Conditioner Model 3MXS24RMVJUA

Integrate maintenance plans directly into your work orders in MaintainX.

Capacitor Voltage Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Main circuit checked for short circuit?

Check mark

Warning: Never touch any live parts during the procedure.

Check mark

Voltage between FU2 and DC–

Check mark

Is the voltage 50 V or less?

Check mark

Ensure firm contact between the multimeter probes and the test points.

Check mark

Sign off on the capacitor voltage check

Run this procedureArrow right

Electronic Expansion Valve Check

Check mark

EV connector correctly inserted in the PCB

Check mark

All EVs generate a latching sound after power cycle

Check mark

Continuity check for EVs not generating a latching sound

Check mark

Outdoor unit PCB check if no EV generates a latching sound

Check mark

EV unit check after mounting a good coil

Check mark

Warning: Operating with a defective electronic expansion valve may cause problems

Run this procedureArrow right

Hall IC Check

Check mark

CDXS, FDXS Series

Check mark

1. Check the connector connection.

Check mark

2. With the power on, operation off, and the connector connected, check the following.

Check mark

(1) Output voltage of about 5 V between pins 1 and 3.

Check mark

(2) Generation of 3 pulses between pins 2 and 3 when the indoor fan motor is operating.

Check mark

If NG in step (1) -> Defective PCB -> Replace the PCB (control PCB).

Check mark

If NG in step (2) -> Defective Hall IC -> Replace the indoor fan motor.

Check mark

If OK in both steps (1) and (2) -> Replace the PCB (control PCB).;

Run this procedureArrow right

Indoor Fan Motor Connector Check

Check mark

CTXG, FTXR, CTXS, FTXS, FVXS Series

Check mark

1. Check the connection of connector.

Check mark

2. Check motor power supply voltage output (pins 4 - 7).

Check mark

3. Check motor control voltage (pins 4 - 3).

Check mark

4. Check rotation command voltage output (pins 4 - 2).

Check mark

5. Check rotation pulse input (pins 4 - 1).

Check mark

FDMQ Series

Check mark

1. Turn the power supply OFF.

Check mark

2. With the fan motor connector disconnected, measure the resistance between each pin, then make sure that the resistance is more than the value mentioned in the following table.

Run this procedureArrow right

Inverter Analyzer Check

Check mark

Warning: This procedure requires trained personnel with PPE!

Check mark

Power turned off?

Check mark

Install an inverter analyzer instead of a compressor.

Check mark

Charged voltage of the built-in smoothing electrolytic capacitor dropped to 10 VDC or below?

Check mark

Terminals removed from the compressor?

Check mark

Terminals connected to the terminals of the inverter analyzer without touching each other?

Check mark

Activate the power transistor test operation from the outdoor unit.

Check mark

Forced cooling operation ON/OFF switch pressed for 5 seconds?

Check mark

Diagnose according to 6 LEDs lighting status.

Run this procedureArrow right

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets