Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Daikin Outdoor Heat Pump RX60G3V1B
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Electronic Expansion Valve Check
EV connector correctly connected to the PCB
EV generates a latching sound when power is turned off and on
Continuity confirmed when connector is disconnected and checked with a multimeter
Continuity between the pins 1 - 6, 3 - 6, 2 - 5, 4 - 5 (between the pins 1 - 6, 2 - 6, 3 - 6, 4 - 6 for the harness 5P models)
If continuity is confirmed in step 3, the outdoor unit PCB is not faulty
Sign off on the electronic expansion valve check
Thermistor Resistance Check
Warning: Ensure the power is off before starting the procedure
Disconnect the connectors of the thermistors from the PCB
Measure the resistance of each thermistor using a multimeter
Remove the PCB from the control PCB to measure the resistance if the room temperature thermistor is soldered on a PCB
Remove the thermistor and measure the resistance if the connector of indoor heat exchanger thermistor is soldered on a PCB
Sign off on the thermistor resistance check
Rotation Pulse Check
Check No.16: Make sure that the voltage of 320 is applied.
1. Set operation off and power off. Disconnect the connector S70.
2. Check that the voltage between the pins 4 - 7 is 320 VDC.
3. Check that the control voltage between the pins 3 - 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 - 4 is 0 ~ 6.5 VDC.
5. Keep operation off and power off. Connect the connector S70.
6. Check whether 4 pulses (0 ~ 15 VDC) are input at the pins 1 - 4 when the fan motor is rotated 1 turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2 → Defective PCB → Replace the outdoor unit PCB (main PCB).
Inverter Analyzer Check
Warning: This procedure requires trained personnel with PPE!
Power turned off?
Install an inverter analyzer instead of a compressor.
Charged voltage of the built-in smoothing electrolytic capacitor dropped to 10 VDC or below?
Terminals removed from the compressor?
Terminals connected to the terminals of the inverter analyzer?
Warning: Do not let the terminals (U,V,W) touch each other. High voltage is applied.
Power transistor test operation activated from the outdoor unit?
Diagnose according to 6 LEDs lighting status.
Indoor Fan Motor Connector Output Check
Check the connection of connector
Check the motor power supply voltage output (pins 4 - 7)
Check the motor control voltage (pins 4 - 3)
Check the rotation command voltage (pins 4 - 2)
Check the rotation pulse (pins 4 - 1)
Sign off on the Indoor Fan Motor Connector Output Check
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX