The Trane Series R™ Helical Rotary Chiller RTAC170S is a high-efficiency industrial cooling solution designed for large commercial applications. Known for its reliability and performance, this chiller offers advanced features to optimize energy consumption and maintain consistent temperature control.
Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Trane Series R™ Helical Rotary Chiller RTAC170S
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Monthly Series R™ Helical Rotary Chiller Maintenance
Perform all weekly maintenance procedures
Record the system subcooling
Make any repairs necessary
1 Weekly Series R™ Helical Rotary Chiller Maintenance
While unit is running in stable conditions.
Check MP pressure for evaporator, condenser and intermediate oil.
Observe liquid line sight glass on EXV.
If liquid line sight glass has bubbles measure the subcooling entering the EXV. The subcooling should never be less than 4 °F under any circumstances.
A clear sightglass alone does not mean that the system is properly charged. Also check the rest of the system operating conditions.
Inspect the entire system for unusual conditions and inspect the condenser coils for dirt and debris. If the coils are dirty, refer to coil cleaning.
Sign off on the weekly maintenance
1 Yearly Series R™ Helical Rotary Chiller Maintenance
Warning: Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
Perform all weekly and monthly procedures
Check oil sump oil level while unit is off
NOTE: Routine changing of the oil is not required. Use an oil analysis to determine the condition of the oil.
Have a qualified laboratory perform a compressor oil analysis to determine system moisture content and acid level
Contact a qualified service organization to leak test the chiller, to check operating and safety controls, and to inspect electrical components for deficiencies
Inspect all piping components for leakage and damage. Clean out any inline strainers
Clean and repaint any areas that show signs of corrosion
Clean the condenser coils
Adding Charge:
This procedure should be followed when adding charge to an undercharged unit. When low charge is indicated by low subcooling in the liquid line, charge should be added until sufficient subcooling is achieved.
1. Attach charging hose to evaporator service valve (3/8” (9mm) flare). Open service valve.
2. Add 10 pounds of refrigerant (R-134a) charge.
3. Close valve, remove charging hose and start unit. Monitor subcooling.
4. If subcooling is still insufficient, return to step #1.
NOTE: Proper subcooling can be determined from run log history, service experience, or by contacting Trane technical service.;
Clearances
Ensure enough space around the outdoor unit for unrestricted access to all service points.
Refer to submittal drawings for the unit dimensions.
Enter the clearance in feet for compressor service (minimum recommended is 4 feet)
Provide sufficient clearance for the opening of control panel doors.
Refer to Figure 18 through Figure 19 for minimum clearances.
Local codes requiring additional clearances will take precedence over these recommendations.
Ensure unobstructed flow of condenser air to maintain chiller capacity and operating efficiency.
Avoid warm air recirculation and coil starvation.
Do not allow debris, trash, supplies etc. to accumulate in the vicinity of the unit.
Access the parts list for your equipment in MaintainX.
Isolator
X10140305620
Isolator
X10140305620
Isolator
X10140305620
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX