The Trane CenTraVac™ Water-Cooled Chiller CVHF model offers efficient cooling solutions for large industrial applications. With a capacity range of 350-570 tons, this chiller is designed for reliability and performance, ensuring optimal operation in demanding environments. Experience advanced technology and energy efficiency with Trane's trusted engineering.
Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Trane CenTraVac™ Water-Cooled Chiller CVHF - 350-570 - 588 - 080S / 080L
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Yearly Purge Unit Inspection
- Shut down the chiller once each year to check the items of Purge Unit
1. Review the purge Installation, Operation, and Maintenance manual and follow maintenance and/or inspection items identified
2. Review purge pump-out data
3. Review overall operation of purge and service as necessary;
1 Yearly Condenser Cleaning
- Clean condenser tubes
NOTICE
Proper Water Treatment Required! The use of untreated or improperly treated water could result in scaling, erosion, corrosion, algae or slime
Use the services of a qualified water treatment specialist to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water
Condenser tube fouling is indicated when the approach temperature (the difference between the condensing refrigerant temperature and the leaving condenser water temperature) is higher than predicted
If the annual condenser tube inspection indicates that the tubes are fouled, two cleaning methods— mechanical and chemical—can be used to rid the tubes of contaminants. Use the mechanical cleaning method to remove sludge and loose material from smooth-bore tubes
To clean other types of tubes including internally- enhanced types, consult a qualified service organization for recommendations
1. Follow all instructions in “Waterbox Removal and Installation,” to remove waterbox covers
2. Work a round nylon or brass bristled brush (attached to a rod) in and out of each of the condenser water tubes to loosen the sludge
3 Yearly Evaporator Maintenance
- Clean evaporator
1. Since the evaporator is typically part of a closed circuit, it may not accumulate appreciable amounts of scale or sludge
2. Normally, cleaning every three years is sufficient
3. However, periodic inspection and cleaning is recommended on open evaporator systems, such as air washers;
1 Yearly Optional Accessories Maintenance
- Shut down the chiller once each year to check the items of Optional Accessories
1. If applicable, lubricate factory-installed gantries
2. After the first month of operation, inspect Heresite® or Belzona® coated waterboxes; thereafter, inspect as needed
3. Inspect anodes
4. Inspect and lubricate hinged waterboxes
5. With water flow sensing option, bleed tubing from waterboxes to transformers;
1 Daily Chiller Maintenance
- Check the chiller’s evaporator and condenser pressures, oil tank pressure, differential oil pressure, and discharge oil pressure
- Compare the readings with the values provided in the general maintenance
- Check the oil level in the chiller oil sump using the two sight glasses provided in the oil sump head. When the unit is operating, the oil level should be visible in the lower sight glass
- Complete logs on a daily basis.
Access the parts list for your equipment in MaintainX.
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.