The Daikin Indoor Cooling/Heating Unit FXMQ15PBVJU is a versatile HVAC solution designed for efficient climate control in residential and commercial spaces. This unit offers reliable heating and cooling performance, ensuring optimal comfort throughout the year. With advanced technology and energy-efficient features, it is an ideal choice for modern indoor environments.
Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Daikin Indoor Cooling/Heating Unit FXMQ15PBVJU
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Electronic Expansion Valve Coil Check
Remove the connector for electronic expansion valve (X7A) from PCB
Check continuity between White and Yellow
Measure resistance value between White and Orange
Measure resistance value between White and Red
Measure resistance value between Yellow and Blue
Measure resistance value between Yellow and Brown
Sign off on the Electronic Expansion Valve Coil Check
Heat Recovery System Maintenance
Check for High Pressure in cooling
Check for High Pressure in heating
Check Thermistor
Check Pressure Sensor
Check for broken wire of the relay wire
Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
Turn OFF the power supply to all equipment
Short circuit between the outdoor-outdoor unit terminal F1 and F2 in the 'Outdoor Unit A'
Conduct continuity checks between the transmission wiring terminal blocks F1 and F2 of the central remote controller using a multimeter
Heat Recovery System Vacuuming/Dehydration Maintenance
Normal vacuuming and dehydration
Vacuum pump enables vacuuming down to –100.7 kPa (–14.6 psi)
Enter the vacuum level after 2 hours of vacuuming
Enter the vacuum level after additional 1 hour of vacuuming if needed
Leak tests conducted if vacuum level does not reach –100.7 kPa (–14.6 psi) after 3 hours
Enter the vacuum level after leaving the compressor in vacuum state for 1 hour
Check if the vacuum gauge reading does not rise after leaving the compressor in vacuum state for 1 hour
Enter the amount of refrigerant charged
Special vacuuming and dehydration - In case of moisture may get mixed in the piping
Power Transistor Check
Warning: Ensure power is OFF before starting the procedure
Power OFF
All wiring removed from the PCB
Type of multimeter prepared
Power supply turned OFF and 10 minutes or more have passed
Measurement mode for analog multimeter
Measurement mode for digital multimeter is diode check mode
Sign off on the power transistor check
Pressure Check
Warning: This procedure requires trained personnel with PPE!
Compressor PI control in cooling
Low pressure protection control
Hot gas bypass control
Superheated degree control in cooling
Superheated degree control in heating
Sign off on the pressure check
Access the parts list for your equipment in MaintainX.
Junction Pipe Kit
KHRP26A250T
Junction Pipe Kit
KHRP26A250T
Junction Pipe Kit
KHRP26A250T
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX













